Heat & Glo LifeStyle 6000GCF-IPILP Indoor Fireplace User Manual


 
Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP • 2110-900 Rev. F • 6/08 15
2. Top Vent - Vertical Termination
No Elbow
Figure 5.6
Figure 5.7
Two Elbows
NOTE: If installing a vertical vent/
termination off the top of the appli-
ance, the ue restrictor should be
used. See Section 7.D.
V
1
V
1
= 50 ft. Max. (15.2 m)
V
1
= 3 ft. Min. (914mm)
V
1
H
1
Maximum V
2
V
1
+ V
2
Minimum
6 in. 152 mm 3 ft 914 mm * * *
1 ft 305 mm 3 ft 914 mm * * *
2 ft 607 mm 6 ft 1.8 m * * *
4 ft 1.2 m 12 ft 3.7 m * * *
V1 + V2 + H1 = 50 ft (15.2 m) Max.
*No speci c restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 50 ft (15.2 m)
V
1
= 6 inches (152 mm) Min.