Heat & Glo LifeStyle 6000GCF-IPILP Indoor Fireplace User Manual


 
Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP • 2110-900 Rev. F • 6/08 13
V
1
H1
Figure 5.3
Figure 5.4
D. Vent Diagrams
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
H
2
H
1
V
1
INSTALLED
HORIZONTALLY
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles
between ceiling restops.
ALWAYS maintain speci ed clearances around
venting and restop systems.
• Install wall shield and ceiling firestops as
speci ed.
Failure to keep insulation or other material
away from vent pipe may cause re.
WARNING
V
1
Minimum H
1
Maximum
6 inches 152 mm 3 ft 914 mm
1 ft 305 mm 3 ft 914 mm
2 ft 610 mm 6 ft 1.8 m
3 ft 914 mm 9 ft 2.7 m
4 ft 1.2 m 12 ft 3.7 m
V
1
+ H
1
= 40 ft (12.2 m) Maximum
H
1
= 20 ft (6.1 m) Maximum
V
1
= 6 inches (152 mm) Minimum
V
1
Minimum H
1
+ H
2
Maximum
1 ft 305 mm Cannot do
1-1/2 ft 457 mm 1-1/2 ft 457 mm
2 ft 610 mm 3 ft 914 mm
3 ft 914 mm 6 ft 1.8 m
4 ft 1.2 m 9 ft 2.7 m
V
1
+ H
1
+ H
2
= 50 ft (15.2 m) Maximum
H
1
+ H
2
= 17 ft (5.2 m) Maximum
V
1
= 1-1/2 ft (457 mm) Minimum
Note: The 6000 series replaces can adapt to
SL series vent pipe, if desired.
When venting off the top of the unit, use a DVP-2SL adapter and
a minimum 48 inch vertical section of SL series vent pipe.
After the 48 inch vertical section, the venting table rules
must be followed. The rst 48 inch vertical section is NOT
counted as part of the vertical components in the table. It is
still counted as part of the overall maximum run. All venting
table rules for the vent run must still be followed.
Example:
DVP pipe 3 ft. min. vertical = 11 ft. max. horizontal
SL pipe 7 ft. min. vertical = 11 ft. max. horizontal
Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZC-
SS termination caps on top vented replaces, a
6 inch minimum vertical vent section is required
before installing rst elbow.
WARNING