Submittal Data HBH SerieS Heat Controller, Inc.
Engineering Design Guide HBH SERIES Heat Controller, Inc.
7
Performance Data: HBH072
Performance capacities shown in thousands of Btuh2400 CFM Nominal Airow Heating & Cooling
WATER/BRINE Cooling - EAT 80/67°F Heating - EAT 70°F
EWT
°F
FLOW
gpm
PD
psi
PD ft. TC SC kW HR EER HC kW HE LAT COP
20
20.00 6.8 15.8 Operation Not Recommended 49.5 5.0 32.5 87.1 2.9
30
10.00 1.2 2.7 82.3 56.8 3.6 94.5 23.0 54.7 5.0 37.5 89.0 3.2
15.00 3.3 7.7 81.1 55.8 3.4 92.8 23.6 56.8 5.1 39.6 89.9 3.3
20.00 6.2 14.3 80.2 55.1 3.4 91.7 23.8 58.0 5.1 40.7 90.3 3.4
40
10.00 1.0 2.2 82.4 57.4 3.9 95.6 21.2 63.2 5.1 45.6 92.3 3.6
15.00 3.0 7.0 82.6 57.1 3.7 95.1 22.4 66.1 5.2 48.4 93.4 3.7
20.00 5.6 13.0 82.4 56.8 3.6 94.6 22.9 67.7 5.2 50.0 94.1 3.8
50
10.00 0.9 2.0 80.7 57.2 4.2 95.1 19.0 72.3 5.3 54.4 95.8 4.0
15.00 2.8 6.5 81.9 57.4 4.0 95.6 20.5 76.0 5.3 57.8 97.2 4.2
20.00 5.3 12.2 82.3 57.4 3.9 95.6 21.1 78.0 5.4 59.7 98.0 4.3
60
10.00 0.5 1.2 77.7 56.3 4.7 93.6 16.7 81.8 5.4 63.3 99.5 4.4
15.00 2.2 5.1 79.7 56.9 4.4 94.7 18.2 86.0 5.5 67.2 101.1 4.6
20.00 4.4 10.1 80.6 57.2 4.3 95.1 18.9 88.3 5.5 69.4 102.0 4.7
70
10.00 0.5 1.1 73.9 54.9 5.2 91.4 14.3 91.1 5.6 72.0 103.1 4.8
15.00 2.1 4.8 76.3 55.8 4.8 92.8 15.8 95.6 5.7 76.3 104.8 4.9
20.00 4.2 9.6 77.5 56.2 4.69 93.5 16.5 98.0 5.7 78.5 105.7 5.0
80
10.00 0.4 0.9 69.4 53.1 5.71 88.9 12.2 99.8 5.8 80.2 106.4 5.1
15.00 1.9 4.5 72.2 54.2 5.37 90.5 13.4 104.4 5.9 84.4 108.2 5.2
20.00 3.9 9.1 73.5 54.7 5.20 91.2 14.1 106.7 5.9 86.5 109.1 5.3
85
10.00 0.4 0.8 67.1 52.1 6.03 87.7 11.2 103.7 5.8 83.8 107.9 5.2
15.00 1.9 4.4 69.8 53.3 5.66 89.2 12.4 108.0 5.9 87.8 109.6 5.3
20.00 3.9 8.9 71.2 53.8 5.49 89.9 13.0 110.1 6.0 89.7 110.4 5.4
90
10.00 0.3 0.8 64.8 51.2 6.35 86.4 10.2 107.6 5.9 87.4 109.4 5.3
15.00 1.8 4.3 67.5 52.3 5.96 87.9 11.3 111.7 6.0 91.1 111.0 5.4
20.00 3.8 8.8 68.9 52.9 5.78 88.6 11.9 113.5 6.0 92.8 111.7 5.5
100
10.00 0.3 0.7 60.1 49.2 7.06 84.2 8.5
Operation Not Recommended
15.00 1.8 4.1 62.7 50.3 6.64 85.4 9.4
20.00 3.7 8.5 64.1 50.9 6.44 86.1 10.0
110
10.00 0.2 0.6 55.8 47.5 7.87 82.7 7.1
15.00 1.7 3.9 58.1 48.4 7.41 83.4 7.8
20.00 3.6
8.3 59.4 48.9 7.19 83.9 8.3
120
10.00 0.2 0.5 52.2 46.3 8.78 82.2 5.9
15.00 1.6 3.7 54.1 46.9 8.27 82.3 6.5
20.00 3.5 8.0 55.1 47.3 8.02 82.5 6.9
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.