Heat Controller 60 HZR-410A Heat Pump User Manual


 
Heat Controller, Inc. HBH SerieS Submittal Data
Heat Controller, Inc. HBH SERIES Engineering Design Guide
14
Blower Performance Data
HBH096 - Standard Unit
SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
3300
BHP 1.01 1.08 1.14 1.21 1.28 1.33 1.39 1.45 1.51 1.58 1.64 1.72 1.78 1.84 1.93 2.00
Sheave/Mtr B A A A A A A A A A C C C C C E
RPM 755 790 820 855 890 915 945 975 1005 1035 1060 1090 1115 1140 1170 1195
Turns
Open
1 5.5 5 4 3.5 3 2.5 2 1.5 1 4 3.5 3 3 2.5 2
3400
BHP 1.08 1.15 1.22 1.29 1.35 1.41 1.47 1.53 1.59 1.68 1.75 1.83 1.90 1.96 2.02 2.08
Sheave/Mtr A A A A A A A A A A C C C C E E
RPM 765 800 835 870 900 930 960 990 1015 1045 1070 1100 1125 1150 1175 1200
Turns
Open
6 5 4.5 4 3.5 3 2.5 2 1.5 1 4 3.5 3 2.5 2 2
3500
BHP 1.16 1.23 1.29 1.36 1.42 1.48 1.54 1.60 1.66 1.73 1.79 1.85 1.92 2.01 2.09 2.17
Sheave/Mtr A A A A A A A A A C C C C E E E
RPM 780 815 845 880 910 940 970 1000 1025 1055 1080 1105 1130 1160 1185 1210
Turns
Open
5.5 5 4.5 3.5 3 2.5 2 1.5 1 4.5 4 3.5 3 2.5 2 1.5
3600
BHP 1.24 1.30 1.37 1.44 1.51 1.58 1.65 1.72 1.78 1.86 1.92 1.98 2.06 2.13 2.21 2.29
Sheave/Mtr A A A A A A A A A C C C E E E E
RPM 795 825 860 890 920 950 980 1010 1035 1065 1090 1115 1145 1165 1190 1215
Turns
Open
5.5 4.5 4 3.5 3 2.5 2 1.5 1 4 3.5 3 2.5 2.5 2 1.5
3700
BHP 1.34 1.40 1.46 1.53 1.61 1.68 1.75 1.82 1.90 1.97 2.06 2.13 2.21 2.28 2.36 2.44
Sheave/Mtr A A A A A A A A C C E E E E E E
RPM 820 850 880 910 940 970 1000 1025 1055 1080 1110 1135 1160 1180 1205 1230
Turns
Open
5 4.5 3.5 3 2.5 2 1.5 1 4.5 4 3.5 3 2.5 2 1.5 1.5
3800
BHP 1.43 1.49 1.56 1.63 1.70 1.78 1.86 1.94 2.02 2.12 2.20 2.28 2.34 2.42 2.50 2.58
Sheave/Mtr A A A A A A A A E E E E E
E E E
RPM 840 870 900 930 960 990 1020 1045 1070 1100 1125 1150 1170 1195 1220 1245
Turns
Open
4.5 4 3.5 3 2.5 2 1.5 1 4 3.5 3 2.5 2.5 2 1.5 1
3900
BHP 1.58 1.64 1.71 1.78 1.85 1.93 2.01 2.09 2.19 2.27 2.35 2.41 2.49 2.57 2.65
Sheave/Mtr A A A A A A D D E E E E E E E
RPM 865 890 920 950 980 1010 1035 1060 1090 1115 1140 1160 1185 1210 1235
Turns
Open
4 4 3 2.5 2 1.5 1 1 4 3.5 3 2.5 2 1.5 1.5
4000
BHP 1.68 1.75 1.83 1.92 2.00 2.08 2.16 2.26 2.34 2.42 2.50 2.56 2.64 2.72 2.80
Sheave/Mtr A A A A D D D E E E E E E E E
RPM 885 910 940 970 1000 1025 1050 1080 1105 1130 1155 1175 1200 1225 1250
Turns
Open
4 3.5 2.5 2.5 2 1 1 4 3.5 3 2.5 2 2 1.5 1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
All Data is Wet Coil
Table Continued from Previous Page