Submittal Data HBH SerieS Heat Controller, Inc.
Engineering Design Guide HBH SERIES Heat Controller, Inc.
13
Blower Performance Data
HBH096 - Standard Unit
All Data is Wet Coil
SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
2400
BHP 0.45 0.50 0.54 0.59 0.63 0.69 0.74 0.80 0.85 0.90 0.94 0.99 1.04 1.10 1.16 1.22
Sheave/Mtr B B B B B A A A A A A A A A C C
RPM 578 625 665 705 745 785 820 860 895 925 960 990 1020 1050 1080 1110
Turns
Open
5 4 3 2.5 1.5 5.5 5 4 3.5 3 2.5 2 1.5 1 4 3.5
2500
BHP 0.50 0.55 0.59 0.64 0.69 0.75 0.81 0.88 0.92 0.97 1.01 1.06 1.12 1.17 1.23 1.29
Sheave/Mtr B B B B A A A A A A A A A C C C
RPM 599 645 685 725 765 800 835 875 905 940 970 1005 1035 1060 1090 1120
Turns
Open
4.5 3.5 2.5 2 6 5 4.5 4 3.5 3 2.5 2 1 4.5 3.5 3
2600
BHP 0.55 0.60 0.65 0.69 0.75 0.80 0.86 0.92 0.97 1.02 1.08 1.13 1.19 1.25 1.30 1.36
Sheave/Mtr B B B B A A A A A A A A A C C C
RPM 625 665 705 740 780 815 850 885 920 950 985 1015 1045 1075 1100 1130
Turns
Open
4 3 2.5 1.5 5.5 5 4.5 3.5 3 2.5 2 1.5 1 4 3.5 3
2700
BHP 0.60 0.65 0.70 0.75 0.80 0.86 0.91 0.97 1.02 1.08 1.14 1.20 1.26 1.32 1.38 1.44
Sheave/Mtr B B B A A A A A A A A A C C C C
RPM 645 685 725 760 795 830 865 900 930 960 995 1025 1055 1085 1115 1140
Turns
Open
3.5 2.5 2 6 5.5 4.5 4 3.5 3 2.5 2 1.5 4.5 4 3.5 3
2800
BHP 0.65 0.71 0.76 0.82 0.87 0.93 0.98 1.04 1.10 1.16 1.21 1.28 1.36 1.43 1.50 1.56
Sheave/Mtr B B B A A A A A A A A A C C C C
RPM 665 705 745 780 810 845 880 910 945 975 1005 1035 1065 1095 1125 1150
Turns
Open
3 2.5 1.5 5.5 5 4.5 4 3 2.5 2 1.5 1 4 3.5 3 2.5
2900
BHP 0.71 0.76 0.82 0.87 0.92 0.98 1.03 1.09 1.16 1.22 1.29 1.36 1.43 1.50 1.57 1.63
Sheave/Mtr B B A A A A A A A A A A C
C C C
RPM 685 720 760 795 825 860 890 920 955 985 1015 1045 1075 1105 1135 1160
Turns
Open
2.5 2 6 5.5 5 4 3.5 3 2.5 2 1.5 1 4 3.5 3 2.5
3000
BHP 0.78 0.84 0.89 0.95 1.00 1.06 1.12 1.18 1.24 1.30 1.37 1.43 1.50 1.58 1.64 1.71
Sheave/Mtr B B A A A A A A A A A C C C C C
RPM 700 740 775 810 845 880 910 940 970 1000 1030 1055 1085 1115 1140 1170
Turns
Open
2.5 1.5 5.5 5 4.5 4 3.5 2.5 2 1.5 1 4.5 3.5 3.5 3 2.5
3100
BHP 0.85 0.91 0.96 1.02 1.08 1.14 1.22 1.29 1.36 1.44 1.50 1.57 1.63 1.70 1.76 1.82
Sheave/Mtr B B A A A A A A A A A C C C C C
RPM 720 755 790 825 860 890 925 955 985 1015 1040 1070 1095 1125 1150 1175
Turns
Open
2 1 5.5 4.5 4 3.5 3 2.5 2 1.5 1 4 3.5 3 2.5 2
3200
BHP 0.93 1.00 1.07 1.14 1.20 1.26 1.32 1.38 1.44 1.51 1.57 1.64 1.70 1.78 1.85 1.92
Sheave/Mtr B A A A A A A A A A C C C C C C
RPM 740 775 810 845 875 905 935 965 995 1025 1050 1080 1105 1135 1160 1185
Turns
Open
1.5 5.5 5 4.5 4 3.5 3 2 1.5 1 4.5 4 3.5 3 2.5 2
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Table Continued on Next Page