Heat Controller 60 HZR-410A Heat Pump User Manual


 
Heat Controller, Inc. HBH SerieS Submittal Data
Heat Controller, Inc. HBH SERIES Engineering Design Guide
8
Performance Data: HBH096
Performance capacities shown in thousands of Btuh3200 CFM Nominal Airow Heating & Cooling
WATER/BRINE Cooling - EAT 80/67°F Heating - EAT 70°F
EWT
°F
FLOW
gpm
PD
psi
PD ft. TC SC kW HR EER HC kW HE LAT COP
20
24.0 10.2 23.5 Operation Not Recommended 67.1 6.60 44.6 87.4 3.0
30
12.0 2.1 4.9 109.6 77.9 4.9 126.2 22.4 73.6 6.73 50.7 89.3 3.2
18.0 5.3 12.1 109.3 77.9 4.7 125.3 23.3 76.9 6.79 53.7 90.2 3.3
24.0 9.3 21.4 108.9 77.8 4.6 124.6 23.7 78.7 6.83 55.4 90.7 3.4
40
12.0 1.9 4.4 108.7 77.3 5.3 126.7 20.7 84.8 6.95 61.1 92.5 3.6
18.0 4.8 11.0 109.5 77.8 5.0 126.5 21.9 89.0 7.03 65.1 93.7 3.7
24.0 8.4 19.3 109.6 77.9 4.9 126.2 22.5 91.4 7.07 67.3 94.4 3.8
50
12.0 1.7 4.0 106.7 76.2 5.7 126.2 18.7 96.7 7.17 72.2 95.9 4.0
18.0 4.5 10.3 108.2 77.0 5.4 126.6 20.1 101.9 7.27 77.1 97.4 4.1
24.0 7.9 18.2 108.8 77.3 5.2 126.7 20.8 104.7 7.32 79.8 98.2 4.2
60
12.0 1.5 3.4 103.6 74.8 6.3 124.9 16.5 108.8 7.40 83.6 99.4 4.3
18.0 3.8 8.8 105.8 75.8 5.9 125.9 18.0 114.9 7.51 89.3 101.2 4.5
24.0 6.8 15.8 106.8 76.3 5.7 126.2 18.8 118.2 7.58 92.4 102.1 4.6
70
12.0 1.3 3.1 99.6 73.1 6.9 123.1 14.5 121.0 7.63 95.0 102.9 4.6
18.0 3.6 8.4 102.4 74.3 6.5 124.4 15.9 127.7 7.76 101.2 104.9 4.8
24.0 6.6 15.2 103.7 74.9 6.2 125.0 16.6 131.3 7.83 104.6 105.9 4.9
80
12.0 1.2 2.8 94.9 71.1 7.6 120.9 12.5 132.8 7.86 106.0 106.3 5.0
18.0 3.4 7.9 98.2 72.5 7.1 122.4 13.8 139.8 8.01 112.5 108.4 5.1
24.0 6.3 14.5 99.7 73.1 6.9 123.2 14.5 143.5 8.09 115.9 109.4 5.2
85
12.0 1.1 2.7 92.3 70.0 8.0 119.6 11.6 138.3 7.98 111.1 107.9 5.1
18.0 3.4 7.7 95.7 71.4 7.5 121.3 12.8 145.3 8.13 117.5 109.9 5.2
24.0 6.2 14.2 97.3 72.1 7.2 122.0 13.5 148.8 8.21 120.8 111.0 5.3
90
12.0 1.1 2.5 89.6 68.9 8.4 118.4 10.6 143.9 8.10 116.2 109.5 5.2
18.0 3.3 7.6 93.2 70.4 7.9 120.1 11.8 150.8 8.25 122.6 111.5 5.4
24.0 6.1 14.0 94.9 71.1 7.6 120.9 12.5 154.2 8.34 125.7 112.5 5.4
100
12.0 1.0 2.3 83.9 66.6 9.3 115.7 9.0
Operation Not Recommended
18.0 3.1 7.2 87.7 68.1 8.7 117.5 10.0
24.0 5.9 13.6 89.6 68.9 8.4 118.3 10.6
110
12.0 0.9 2.0 77.8 64.0 10.4 113.1 7.5
18.0 3.0 6.8 81.7 65.7 9.7 114.8 8.4
24.0 5.7
13.1 83.7 66.5 9.4 115.6 8.9
120
12.0 0.8 1.8 71.5 61.2 11.5 110.6 6.2
18.0 2.8 6.5 75.4 63.0 10.8 112.2 7.0
24.0 5.5 12.6 77.4 63.8 10.4 113.0 7.4
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.