Heat Controller 60 HZR-410A Heat Pump User Manual


 
Submittal Data HBH SerieS Heat Controller, Inc.
Engineering Design Guide HBH SERIES Heat Controller, Inc.
15
Blower Performance Data
HBH120 - Standard Unit
All Data is Wet Coil
SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
3000
BHP 0.75 0.81 0.86 0.91 0.97 1.03 1.09 1.15 1.21 1.27 1.34 1.41 1.47 1.54 1.61 1.67
Sheave/Mtr B B B B B B A A A A A A A A A A
RPM 680 720 755 790 825 860 895 925 955 985 1015 1045 1070 1100 1130 1155
Turns Open 5 4 3.5 3 2.5 1.5 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1
3100
BHP 0.82 0.88 0.94 0.99 1.04 1.10 1.17 1.26 1.33 1.40 1.46 1.53 1.59 1.66 1.72 1.80
Sheave/Mtr B B B B B A A A A A A A A A A C
RPM 700 735 775 805 840 875 905 940 970 1000 1025 1055 1080 1110 1135 1165
Turns Open 4.5 4 3 2.5 2 6 5.5 4.5 4.5 3.5 3 3 2.5 2 1.5 4
3200
BHP 0.90 0.96 1.03 1.10 1.17 1.23 1.29 1.35 1.41 1.47 1.55 1.61 1.68 1.74 1.81 1.89
Sheave/Mtr B B B B B A A A A A A A A A A C
RPM 720 755 790 825 860 890 920 950 980 1010 1040 1065 1095 1120 1145 1175
Turns Open 4 3.5 3 2 1.5 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1 3.5
3300
BHP 0.98 1.04 1.11 1.18 1.25 1.31 1.37 1.43 1.49 1.55 1.62 1.68 1.75 1.81 1.88 1.95
Sheave/Mtr B B B B A A A A A A A A A A A C
RPM 740 770 805 840 875 905 935 965 995 1020 1050 1075 1105 1130 1155 1180
Turns Open 4 3 2.5 2 6 5.5 5 4 4 3 2.5 2.5 2 1.5 1 3.5
3400
BHP 1.06 1.13 1.19 1.26 1.33 1.38 1.44 1.50 1.56 1.65 1.72 1.80 1.87 1.94 2.00 2.06
Sheave/Mtr B B B B A A A A A A A A A A C C
RPM 755 790 820 855 890 915 945 975 1005 1035 1060 1090 1115 1140 1165 1190
Turns Open 3.5 3 2.5 1.5 6 5 4.5 4 3.5 3 2.5 2 1.5 1 4 3
3500
BHP 1.14 1.21 1.27 1.34 1.40 1.46 1.52 1.58 1.65 1.71 1.77 1.84 1.90 1.98 2.06 2.14
Sheave/Mtr B B B A A A A A A A A A A A C C
RPM 770
805 835 870 900 930 960 990 1020 1045 1070 1100 1125 1150 1175 1200
Turns Open 3 2.5 2 6 5.5 5 4.5 3.5 3.5 3 2.5 2 1.5 1 3.5 3
3600
BHP 1.23 1.29 1.36 1.42 1.50 1.57 1.64 1.71 1.77 1.84 1.90 1.96 2.05 2.13 2.21 2.27
Sheave/Mtr B B B A A A A A A A A A A C C C
RPM 790 820 855 885 915 945 975 1005 1030 1060 1085 1110 1140 1165 1190 1210
Turns Open 3 2.5 1.5 6 5.5 4.5 4 3.5 3 2.5 2 1.5 1.5 4 3.5 3
3700
BHP 1.32 1.38 1.44 1.51 1.58 1.65 1.73 1.81 1.88 1.96 2.03 2.10 2.18 2.26 2.34 2.42
Sheave/Mtr B B A A A A A A A A A A A C C C
RPM 810 840 870 900 930 960 990 1020 1045 1075 1100 1125 1150 1175 1200 1225
Turns Open 2.5 2 6 5.5 5 4.5 4 3 3 2.5 2 1.5 1 3.5 3 2.5
3800
BHP 1.41 1.47 1.54 1.61 1.68 1.75 1.82 1.91 1.99 2.07 2.17 2.25 2.31 2.39 2.47 2.55
Sheave/Mtr B B A A A A A A A A A A A C C C
RPM 830 860 890 920 950 980 1005 1035 1060 1085 1115 1140 1160 1185 1210 1235
Turns Open 2 1.5 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1 1 3.5 3 2.5
3900
BHP 1.54 1.60 1.67 1.74 1.82 1.89 1.96 2.04 2.14 2.22 2.30 2.38 2.46 2.52 2.60 2.68
Sheave/Mtr B A A A A A A A A A A A C C C C
RPM 850 875 905 935 965 995 1020 1045 1075 1100 1125 1150 1175 1195 1220 1245
Turns Open 2 6 5.5 5 4.5 3.5 3 2.5 2.5 2 1.5 1 3.5 3 2.5 2
4000
BHP 1.63 1.71 1.78 1.86 1.94 2.03 2.11 2.19 2.27 2.37 2.45 2.51 2.59 2.67 2.75 2.85
Sheave/Mtr A A A A A A A A A A A A C C C C
RPM 865 895 920 950 980 1010 1035 1060 1085 1115 1140 1160 1185 1210 1235 1260
Turns Open 6 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1 1 3.5 3 2.5 2
4100
BHP 1.73 1.81 1.90 1.97 2.05 2.12 2.20 2.27 2.34 2.42 2.52 2.62 2.70 2.80 2.90
Sheave/Mtr A A A A A
A A A A A A C C C C
RPM 885 915 945 970 1000 1025 1055 1080 1105 1130 1155 1180 1200 1225 1250
Turns Open 6 5.5 4.5 4 4 3 2.5 2 2 1.5 1 3.5 3 2.5 2
4200
BHP 1.87 1.94 2.02 2.08 2.16 2.24 2.32 2.40 2.48 2.58 2.68 2.76 2.86 2.96
Sheave/Mtr A A A A A A A A A A C C C C
RPM 905 935 965 990 1020 1045 1070 1095 1120 1145 1170 1190 1215 1240
Turns Open 5.5 5 4.5 4 3.5 3 2.5 2 1.5 1 3.5 3.5 3 2.5
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Table Continued on Next Page