Heat Controller 60 HZR-410A Heat Pump User Manual


 
Heat Controller, Inc. HBH SerieS Submittal Data
Heat Controller, Inc. HBH SERIES Engineering Design Guide
20
HBH Electrical Data
Standard
HB
Model
Voltage
Code
Rated
Voltage
Voltage
Min Max
Blower
Option
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY RLA LRA
072
H
208-3-60 197/254 A, B, C 2 10.4 73.0 4.0 24.8 27.4 35
H
208-3-60 197/254 D, E 2 10.4 73.0 6.2 27.0 29.6 35
F
460-3-60 414/506 A, B, C 2 5.8 38.0 2.0 13.6 15.1 20
F
460-3-60 414/506 D, E 2 5.8 38.0 3.1 14.7 16.1 20
N
575-3-60 518/633 A, B, C 2 3.8 36.5 1.4 9.0 9.9 15
N
575-3-60 518/633 D, E 2 3.8 36.5 2.3 9.9 10.8 15
096
H
208-3-60 197/254 A, B, C 2 13.7 83.1 6.2 33.6 37.0 50
H
208-3-60 197/254 D, E 2 13.7 83.1 9.2 36.6 40.0 50
F
460-3-60 414/506 A, B, C 2 6.2 41.0 3.1 15.5 17.0 20
F
460-3-60 414/506 D, E 2 6.2 41.0 4.3 16.7 18.3 20
N
575-3-60 518/633 A, B, C 2 4.8 33.0 2.3 11.9 13.1 15
N
575-3-60 518/633 D, E 2 4.8 33.0 3.4 13.0 14.2 15
120
H
208-3-60 197/254 A, B, C 2 15.6 110.0 9.2 40.4 44.3 50
H
208-3-60 197/254 D, E 2 15.6 110.0 14.1 45.3 49.2 60
F
460-3-60 414/506 A, B, C 2 7.8 52.0 4.3 19.9 21.9 25
F
460-3-60 414/506 D, E 2 7.8 52.0 7.0 22.6 24.6 30
N
575-3-60 518/633 A, B, C 2 5.8 38.9 3.4 15.0 16.5 20
N
575-3-60 518/633 D, E 2 5.8 38.9 5.2 16.8 18.3 20
HACR circuit breaker in USA only
All fuses Class RK-5