Heat Controller 60 HZR-410A Heat Pump User Manual


 
Heat Controller, Inc. HBH SerieS Submittal Data
Heat Controller, Inc. HBH SERIES Engineering Design Guide
12
Blower Performance Data
HBH072 - Standard Unit
All Data is Wet Coil
SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50
1800
BHP 0.28 0.32 0.35 0.39 0.42 0.45 0.48 0.52 0.56 0.60 0.64 0.69 0.72 0.76
Sheave/Mtr B B B A A A A A A C C C C C
RPM 599 645 690 735 775 815 850 885 910 940 965 995 1015 1040
Turns Open 3 2 1 4 3.5 2.5 2 1.5 1 5 4.5 4 3.5 3
1900
BHP 0.31 0.36 0.40 0.44 0.49 0.53 2.50 0.62 0.65 0.69 0.73 0.76 0.80 0.84
Sheave/Mtr B B A A A A A A C C C C C C
RPM 604 655 695 740 780 820 855 890 920 950 980 1005 1030 1055
Turns Open 3 2 5 4 3 2.5 2 1.5 5.5 4.5 4 3.5 3 3
2000
BHP 0.31 0.34 0.39 0.45 0.50 0.54 0.59 0.63 0.67 0.72 0.75 0.79 0.82 0.86 0.90
Sheave/Mtr B B B A A A A A A C C C C C C
RPM 568 615 660 705 750 785 825 860 895 930 960 990 1015 1040 1065
Turns Open 4.5 2.5 1.5 4.5 3.5 3 2.5 1.5 1 5 4.5 4 3.5 3 2.5
2100
BHP 0.33 0.38 0.42 0.46 0.50 0.54 0.59 0.65 0.70 0.74 0.78 0.81 0.85 0.89 0.94 0.98
Sheave/Mtr B B B A A A A A A A C C C C C C
RPM 531 583 630 670 715 755 795 835 875 905 940 970 1000 1025 1055 1080
Turns Open 4.5 3.5 2 5 4.5 3.5 2.5 2 1.5 1 5 4 4 3 2.5 2.5
2200
BHP 0.37 0.40 0.45 0.49 0.55 0.60 0.65 0.70 0.75 0.79 0.83 0.87 0.92 0.96 1.00 1.04
Sheave/Mtr B B B A A A A A A C C C C C E E
RPM 552 599 645 685 730 770 810 850 885 915 950 980 1010 1040 1065 1090
Turns Open 4 3 2 5 4 3 2.5 2 1.5 5.5 4.5 4 3.5 3 2.5 2
2300
BHP 0.42 0.47 0.51 0.56 0.60 0.65 0.70 0.75 0.80 0.84 0.89 0.94 1.00 1.05 1.10 1.16
Sheave/Mtr B B B A A A A A A C C C E E E E
RPM 573 620 660 705 745 785 820 860 895 925 960 990 1020 1050 1075 1105
Turns Open 3.5 2.5 1.5 4.5
4 3 2.5 1.5 1 5 4.5 4 3.5 3 2.5 2
2400
BHP 0.48 0.52 0.57 0.61 0.66 0.72 0.78 0.83 0.87 0.92 0.97 1.02 1.07 1.13 1.19 1.25
Sheave/Mtr B B A A A A A A A C C E E E E E
RPM 604 645 690 730 765 805 845 880 910 945 975 1010 1035 1065 1095 1125
Turns Open 3 2 5 4 3.5 2.5 2 1.5 1 5 4 3.5 3 2.5 2 1.5
2500
BHP 0.52 0.57 0.61 0.66 0.72 0.78 0.83 0.89 0.94 1.00 1.03 1.08 1.14 1.20 1.25 1.31
Sheave/Mtr B B A A A A A A C E E E E E E E
RPM 620 660 700 740 780 815 850 885 920 950 985 1015 1045 1075 1100 1130
Turns Open 2.5 1.5 4.5 4 3 2.5 2 1.5 5.5 4.5 4 3.5 3 2.5 2 1.5
2600
BHP 0.56 0.61 0.66 0.70 0.76 0.82 0.88 0.93 0.98 1.04 1.08 1.14 1.20 1.26 1.32 1.37
Sheave/Mtr B A A A A A A A C E E E E E E E
RPM 635 675 715 750 790 825 860 895 925 960 990 1020 1050 1080 1110 1135
Turns Open 2.5 5 4.5 3.5 3 2 1.5 1 5 4.5 4 3.5 3 2.5 1.5 1.5
2700
BHP 0.61 0.66 0.71 0.76 0.82 0.87 0.93 0.98 1.04 1.10 1.15 1.21 1.27 1.33 1.39 1.45
Sheave/Mtr B A A A A A A A E E E E E E E E
RPM 655 695 730 770 805 840 875 905 940 970 1000 1030 1060 1090 1120 1145
Turns Open 2 4.5 4 3.5 2.5 2 1.5 1 5 4.5 3.5 3 2.5 2 1.5 1
2800
BHP 0.66 0.72 0.77 0.83 0.88 0.93 0.99 1.05 1.11 1.16 1.22 1.30 1.37 1.44 1.51 1.57
Sheave/Mtr B A A A A A A D E E E E E E E E
RPM 670 710 750 785 815 850 885 915 950 980 1010 1040 1070 1100 1130 1155
Turns Open 1.5 4.5 3.5 3 2.5 1.5 1.5 1 4.5 4 3.5 3 2.5 2 1.5 1
2900
BHP 0.71 0.77 0.82 0.87 0.93 0.98 1.04 1.10 1.16 1.22 1.30 1.36 1.43 1.50 1.57 1.63
Sheave/Mtr A A A A A A D E E E E E E E E E
RPM 685 725 765 795 830 860 895
925 955 985 1020 1045 1075 1105 1135 1160
Turns Open 5 4 3.5 3 2 1.5 1 5 4.5 4 3.5 3 2.5 1.5 1 1
3000
BHP 0.79 0.84 0.90 0.95 1.01 1.07 1.13 1.19 1.25 1.31 1.38 1.46 1.52 1.59 1.66
Sheave/Mtr A A A A A D D E E E E E E E E
RPM 710 745 780 815 850 885 915 945 975 1005 1035 1065 1090 1120 1150
Turns Open 4.5 4 3 2.5 2 1 1 5 4 3.5 3 2.5 2 1.5 1
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require eld selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.