Heat Controller 60 HZR-410A Heat Pump User Manual


 
Submittal Data HBH SerieS Heat Controller, Inc.
Engineering Design Guide HBH SERIES Heat Controller, Inc.
5
Performance Data
AHRI/ASHRAE/ISO 13256-1
ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
HBH072 69,000 13.3 92,500 5.0 78,500 19.7 75,500 4.4 71,000 14.6 58,000 3.5
HBH096 95,000 13.7 123,000 5.0 104,500 20.0 101,000 4.4 98,000 15.2 77,000 3.6
HBH120 119,000 13.3 160,000 4.6 134,000 19.3 132,500 4.0 122,500 14.5 103,000 3.3
Note 1: All HBH072 ratings @ 2400CFM (1133 l/s) w/20GPM (1.26 l/s). Sheave setting for AHRI is 2.5 turns open.
Note 2: All HBH096 ratings @ 3200CFM (1510 l/s) w/24GPM (1.51 l/s). Sheave setting for AHRI is 3.0 turns open.
Note 3: All HBH120 ratings @ 4000CFM (1888 l/s) w/30GPM (1.89 l/s). Sheave setting for AHRI is 3.0 turns open.
Note 4: Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
Note 5: Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
Note 6: All ratings based upon operation at lower voltage of dual voltage rated models.
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C
Capacity
Watts
EER W/W
Capacity
Watts
COP
Capacity
Watts
EER W/W
Capacity
Watts
COP
Capacity
Watts
EER W/W
Capacity
Watts
Heating
COP
HBH072 20,223 3.9 27,110 5.0 23,007 5.8 22,128 4.4 20,809 4.3 16,999 3.5
HBH096 27,843 4.0 36,049 5.0 30,627 5.9 29,601 4.4 28,722 4.5 22,567 3.6
HBH120 34,877 3.9 46,893 4.6 39,273 5.7 38,834 4.0 35,903 4.2 30,188 3.3
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
All ratings based upon operation at lower voltage of dual voltage rated models