Harman Stove Company FireLuxe Direct Vent Gas Stove With Top Cooking Burner System Stove User Manual


 
7
INSTALLATION
The gas stove is shipped with a flexible connector that has a 1/2” NPT female connection. The gas supply
piping should have a separate gas shutoff valve and a 1/8” NPT plugged tapping upstream of the valve. The
stove and its main control valve must be disconnected from the gas supply piping system during any pres-
sure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The stove must be isolated from
the gas supply piping system by closing the main control valve during any pressure testing of the gas supply
system at test pressures equal to or less than 1/2 psi (3.5 kPa). After the gas supply has been connected,
apply a soapy water solution to all the fittings to check for gas leaks. Never use a flame to test for leaks.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
This product must be installed by a licensed plumber or gas fitter when installed within the Com-
monwealth of Massachusetts. If this appliance is installed in a dwelling, building or structure used in
whole or in part for residential purposes and the installation includes a horizontal vent termination
that is less than seven (7) feet above the finished grade in the area of the venting, including but not
limited to decks and porches, a hard-wired carbon monoxide detector with an alarm and battery
back-up must be installed on the floor level of the dwelling, building or structure where the appli-
ance is to be installed.
Additionally, a hard-wired or battery operated carbon monoxide detector with an alarm must be in-
stalled on each additional level of the dwelling, building or structure served by the appliance. It shall
be the responsibility of the property owner to secure the services of qualified licensed professionals
for the installation of hard-wired carbon monoxide detectors.
In the event that the horizontally vented appliance is installed in a crawl space or attic, the hard-
wired carbon monoxide detector with alarm and battery back-up may be installed on the next adja-
cent floor level.
In the event that this requirement cannot be met at the time of completion of the installation of the
appliance, the owner shall have a period of thirty (30) days to comply with the requirement. How-
ever, during said thirty (30) day period, a battery operated carbon monoxide detector with alarm
must be installed.
Each carbon monoxide detector as required in accordance with the above provisions must comply
with NFPA 720 and be ANSI/UL 2034 and IAS certified.
In addition when the stove is horizontally vented and the vent termination is less than seven (7) feet
above finished grade a metal or plastic identification plate must be permanently mounted to the exte-
rior of the building at a minimum height of eight (8) feet above grade directly in line with the ex-
haust vent terminal. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
A COPY OF THESE INSTRUCTIONS PLUS ALL VENTING INSTRUCTIONS WHICH IN-
CLUDE PARTS LISTS, AND/OR ALL VENTING DESIGN INSTRUCTIONS MUST REMAIN
WITH THE STOVE AT THE COMPLETION OF THE INSTALLATION.
ATTENTION INSTALLERS: Mark below which venting system was used in the installation. These
instructions must remain with the FireLuxe Installation & Operation Manual.
Simpson DuraVent GS
AmeriVent Direct Security Secure Vent Selkirk DT
To avoid confusion discard the all vent manufacturers instructions that do not apply to this installation.
NOTE: If you will be installing the optional warming shelves, make sure to plan for the additional width
that they occupy. For the details, see the information included with the warming shelf kit.