Page 6-6 TS-TPI DATA AND REPORTS
TS-TPI Installation and Wiring Guide
CALIBRT Menu
CALIBRT (User Interface)
Description of Steps:
Here is the SELECT DIAGNOSTIC OPTION
menu displaying RESET and CALIBRT.
1) Press the M2 key under CALIBRT.
The CALIBRATE PUMP N display asks if the
user is sure before enabling automatic
calibration for a particular pump controller;
giving the user a chance to press CANCEL
to abort the calibration process.
2) Press the ENTER key to enable calibra-
tion for the pump controller.
Press the CANCEL key to
abort the process.
In the following examples, “N”
represents any pump number -
1, 2, 3 and so on.
NOTE
SELECT DIAGNOSTIC OPTION
RESET CALIBRT
M1 M2 M3 M4
RESET PUMP 1
ARE YOU SURE?
CANCEL
ENTER
(For STP-SCI controller only) After enabling calibration, the display will flash the word DONE... for a
few seconds and then it will automatically return to the SELECT DIAGNOSTIC OPTION menu,
displaying RESET and CALIBRT.
Follow the Calibration Procedure steps below to complete STP-SCI calibration. For further details on
the calibration process see the STP-SCI Installation and Owner’s manual.
Calibration Procedure
1) Prevent product flow out of the STP by closing a ball valve at the pump discharge.
2) When calibration is enabled, the green, red and yellow LEDs on the pump controller will blink.
3) Turn on the hook signal to begin calibration process. The controller takes a snap shot of the
voltage, current and power (these are the Calibration status values seen in the Display Menu men-
tioned earlier).
4) The calibration process is complete when the red LED stops flashing. The green LED will remain
flashing on stand alone TPCs and the green and yellow remain flashing in Master/Slave or Alternating
configured TPCs.
5) Turn off the hook.
6) Verify that the Tank Sentinel display has returned to the RUN MODE, showing SYSTEM, TANK,
SENSOR, etc. are all OKAY.
7) Refer to the STP-SCI Installation and Owner’s Manual Troubleshooting Guide if the pump does not
start or an alarm condition is present on the controller.