Franklin TS-TPI Water Pump User Manual


 
6
Page 6-4 TS-TPI DATA AND REPORTS
TS-TPI Installation and Wiring Guide
TPI Diagnostic Function Notes
The diagnostic function allows the user to command the pump controllers from the Tank Sentinel
console. The user is able to issue resets to clear faults and enable calibration.
To access this function, the user first presses the MENU key, then DIAG, then PUMPS and then
PUMP #. The tank gauge allows the user to select a pump number and will then display the
diagnostic function keys RESET and CALIBRT.
If the user selects the RESET function, the Tank Sentinel will ask, “ARE YOU SURE?” and if the
user presses the ENTER key, then the reset will be performed. Pressing ENTER in response to the
question will issue the reset to the controller. If the user is not sure about the reset, perhaps due to
a safety concern, then the user should press the CANCEL key to abort this operation.
The CALIBRT function is for STP-SCI TPC only. For details of the calibration process see the STP-
SCI Installation and Owner’s manual. When a user selects the CALIBRT function, the Tank
Sentinel asks “ARE YOU SURE?” Pressing ENTER enables calibration on the selected pump
controller. Pressing cancel aborts the operation. When calibration is enabled, the STP-SCI
memory is erased. For proper calibration no product flow can go out of the pump. Close a ball
valve at the pump discharge or turn down the pump’s clamp valve before calibrating. During the
calibration process the TPC takes a snap shot of the voltage, current and power of the pump.
These values are displayed as are the Calibrated status values in the Display Menu.
DIAG Menu
PUMPS (User Interface)
Description of Steps:
1) Press the MENU key and follow the highlighted sequences...
The SELECT MENU OPTION menu is shown.
2) Press the DOWN key once...
Here is the second SELECT MENU OPTION
menu.
3) Press the M2 key to show the DIAG menu.
Here is the main DIAG menu.
4) Press the M1 key to display the SELECT
DANGER!
The potential for electric
shock exists! Verify the site
is safe! -- before proceeding
with a Reset operation.
H U
MENU
7
K X
DOWN
SPACE
SELECT MENU OPTION (MORE)
SETUP UPGRADE LANGUAGE DATALOG
SELECT MENU OPTION (MORE)
DISPLAY DIAG
M1 M2 M3 M4