Franklin TS-TPI Water Pump User Manual


 
4
Page 4-10 TS-TPI SETUP PROGRAMMING
TS-TPI Installation and Wiring Guide
RESERVE (user entry)
Description of Steps:
Here is the GROUP 2 main menu, displaying
TYPE, MODE and RESERVE...
1) Press the M3 key to display the RESERVE
menu...
Here is the RESERVE user entry field display-
ing the “percent full” value for GROUP 2 (in
Priority mode). The default setting is 20.
2) Press the M4 key to backspace and erase
the default percent value. this will clear the
field.
3) Use the keypad to enter a percent value for
each group.
4) Press the ENTER key to accept data entry.
This entry returns the display to the GROUP N
menu, displaying TYPE, MODE, and RE-
SERVE.
5) Press the CANCEL key to return to the TPI
GROUP menu, displaying GROUP 1 to
GROUP 4.
Proceed to the next group number menu.
Repeat the steps above to set the reserve
percent for each group that is in Priority Mode.
Exiting Setup Mode
EXIT SETUP (user entry)
Description of Steps:
1)Press the CANCEL key to return to the main TPI menu, which displays ENABLE, PUMP and
GROUP.
This completes the Setup Programming for the TPI device.
2) Press the CANCEL key to return to the TPI SETUP MENU menu, which displays TPI.
3) Press the CANCEL key to return to the main SETUP MENU menu, which displays EXIT, SYSTEM,
TANKS and PROBES.
4) Press the M1 key under the word EXIT to return the ATG to RUN MODE.
GROUP 2
TYPE MODE RESERVE
M1 M2 M3 M4
RESERVE PERCENT GROUP 2 NUMERIC
20 BACKSPACE
M1 M2 M3 M4
ENTER
When set up programming is completed, follow the Exiting Setup Mode
steps (next section) to return the Tank Sentinel to the Run Mode.