Table 10.2
Remote Display Diagnostic Messages (continued)
MESSAGE TYPE EXPLANATION
Lockout Main flame was not established during the main burner trial for ignition.
Lockout Main valve has been energized and main flame proven during trial
for ignition.
Status Pilot valve (strip J2, terminal 5) is de-energized and main flame is on.
Lockout Main valve proof-of-closure is open before startup or after burner
shutdown.
Lockout Pilot flame was not established during the pilot trial for ignition.
Status Pilot flame is proven; transformer is de-energized; remaining
countdown for pilot trial for ignition is “XX”.
Status Pilot valve and ignition transformer are energized; countdown for
pilot trial for ignition begins at “XX”.
Lockout An external source of voltage is present on the ignition, pilot or
main output terminals.
Status 15 second post purge is started on burner shutdown; “XX” shows
countdown.
Lockout DIP switch improperly set or changed during cycle.
Status Modulating motor is sent to high fire; “XX” shows purge countdown.
Status Part of the optional history log which records the total number of
operating cycles and the last lockout messages up to a maximum
of 10.
Lockout Internal relay(s) fail initial check. Check ratings. If lockout still oc-
curs after overload is eliminated, replace control.
Status Control has completed internal safe-start check.
Status Combustion air switch is closed before start-up or after shut-
down; control holds start-up until switch re-opens; if interlocks
close before switch opens, alarm will energize in 30 seconds.
Lockout Same conditions as above, except the interlocks closed for 30 sec-
onds before the switch re-opened, causing a lockout and the alarm.
MAIN # ( ) FAILED
MAIN FLAME ON
MAIN FLAME ON
PILOT OFF
MAIN VALVE FAIL
LKOUT XXXX:XX:XX
PILOT FLAME FAIL
LKOUT XXXX:XX:XX
PILOT ON
XX
PILOT TRIAL FOR
IGNITION XX
PLT/MVL ENERGIZ.
XX:XX:XX LOCKOUT
POST PURGE
XX
PROGM SWITCH ERR
LKOUT XXXX:XX:XX
PURGE AT HIGH
FIRE XX
RECORD #X
RELAY FAIL
LKOUT XXXX:XX:XX
SAFE START OK
UNSAFE AIR SHORT
UNSAFE AIR SHORT
LKOUT XXXX:XX:XX