Table 10.1
Bi-Flame Operating Sequence (continued)
BURNER START-UP
Is voltage present at air flow switch
within ten seconds?
Is flame signal present?
(see next page)
After “XX” equals zero (0)...
Spark energized until pilot flame
proven; pilot valve energized for
countdown of “XX” seconds
(“XX” equals selected trial for
ignition).
Is pilot flame signal present?
YES NO
Is flame signal present?
YES NO
X = burner number.
ERROR MESSAGE
PILOT # (0X) FAILED
LKOUT XXXX:XX:XX
ERROR MESSAGE
MAIN # (0X) FAILED
LKOUT XXXX:XX:XX
Countdown of “XX” seconds
as set by DIP switch.
NORMAL MESSAGE
PURGE AT HIGH
FIRE XX
Modulator sent to low fire.
NORMAL MESSAGE
WAIT FOR LO.FIRE
SWITCH XX:XX
NORMAL MESSAGE
PILOT ON
XX
NORMAL MESSAGE
MAIN FLAME ON
NORMAL MESSAGE
PILOT TRIAL FOR
IGNITION XX
YES NO
YES NO
Is voltage present
at low fire input?
ERROR MESSAGE
AIR NOT PROVEN
LKOUT XXXX:XX:XX
ERROR MESSAGE
LOW FIRE FAIL
LKOUT XXXX:XX:XX
NORMAL MESSAGE
AIR PROVEN
Modulator sent to high fire.
NORMAL MESSAGE
WAIT FOR HI. FIRE
SWITCH XX:XX
YES NO
Is voltage present
at high fire input?
ERROR MESSAGE
HIGH FIRE FAIL
LKOUT XXXX:XX:XX
X = burner number.
Delay 5 seconds.
NORMAL MESSAGE
PILOT ON
IGNITION OFF