Eclipse Combustion 6500 Burner User Manual


 
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
33
Yearly Checklist
1. Test (leak test) safety shut-off valves for tightness of closure.
2. Test pressure switch settings by checking switch movements against pressure
setting and comparing with actual impulse pressure.
3. Visually check ignition cable and connectors.
4. Make sure that the following components are not damaged or distorted:
• the burner nozzle
• the spark plugs
• the flame sensors