HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (L/S) x TEMP. DIFF. (DEG. C) x FLUID FACTOR* =
(kW)
SUPERHEAT = SUCTION TEMPERATURE – SUCTION DEW POINT TEMPERATURE
=
(DEG C)
SUBCOOLING = DISCHARGE BUBBLE POINT TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG C)
*Use 4.16 for water, 4.03 for antifreeze.
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
°
C
°
C
AIR
COIL
°
C
kPa
WATEROUT
WATERIN
°
C
kPa
LOOK UP PRESSURE DROP INTABLE 10
TO DETERMINE FLOW RATE
°
C
LIQUID LINE
kPa
°
C
DEW
POINT
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
°
C
°
C
AIR
COIL
°C
kPa
WATEROUT
WATERIN
°C
kPa
LOOK UP PRESSURE DROP INTABLE 10
TO DETERMINE FLOW RATE
°C
LIQUID LINE
kPa
°
C
DEW
POINT