Carrier 50RHE006-060 Air Conditioner User Manual


 
17
AIR COIL — To obtain maximum performance, clean the air
coil before starting the unit. A ten percent solution of dish-
washing detergent and water is recommended for both sides of
the coil. Rinse thoroughly with water.
FIELD SELECTABLE INPUTS
Jumpers and DIP (dual in-line package) switches on the
control board are used to customize unit operation and can be
configured in the field.
C Control Jumper Settings (See Fig. 9 and 10)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the
limit, DO NOT clip the jumper. To select –12.2 C as the limit,
clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-
TING Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit,
DO NOT clip the jumper. To select –12.2 C as the limit, clip
the jumper.
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or
to remain as a dry contact (no connection). To connect AL2 to
R, do not clip the jumper. To set as dry contact, clip the jumper.
C Control DIP Switches — The C Control has 1 DIP
switch block with five switches. See Fig. 9 and 10.
PERFORMANCE MONITOR (PM) — DIP switch 1 will
enable or disable this feature. To enable the PM, set the switch
to ON. To disable the PM, set the switch to OFF.
STAGE 2 DIP switch 2 will enable or disable compressor
delay. Set DIP switch to OFF for stage 2 in which the compres-
sor will have a 3-second delay before energizing.
SWITCHES 3 AND 4 — Not used.
1 OR 3 TRIES — DIP switch 5 provides selection of whether
there are 1 or 3 tries for FP1 and FP2. This only applies to FP1
and FP2, and not to any other faults. Set DIP switch 5 to ON
for1tryortoOFFfor3tries.
NOTE: The alarm relay will not cycle during Test mode if
switch is set to OFF, stage 2.
D Control Jumper Settings (See Fig. 11 and 12)
WATER COIL FREEZE PROTECTION (FP1) LIMIT
SETTING — Select jumper 3, (JW3-FP1 Low Temp) to
choose FP1 limit of –12.2 C or –1.1 C. To select –1.1 C as the
limit, DO NOT clip the jumper. To select –12.2 C as the limit,
clip the jumper.
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-
TING Select jumper 2 (JW2-FP2 Low Temp) to choose
FP2 limit of –12.2 C or –1.1 C. To select –1.1 C as the limit,
DO NOT clip the jumper. To select –12.2 C as the limit, clip
the jumper.
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2
Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or
to remain as a dry contact (no connection). To connect AL2 to
R, do not clip the jumper. To set as dry contact, clip the jumper.
LOW PRESSURE SETTING — The D Control can be con-
figured for Low Pressure Setting (LP). Select jumper 1
(JW1-LP Norm Open) for choosing between low pressure
input normally opened or closed. To configure for normally
closed operation, do not clip the jumper. To configure for
normally open operation, clip the jumper.
D Control DIP Switches The D Control has 2 DIP
switch blocks. Each DIP switch block has 8 switches and is
labeled either S1 or S2 on the circuit board. See Fig. 11 and 12.
DIP SWITCH BLOCK 1 (S1) This set of switches offers
the following options for D Control configuration:
Performance Monitor (PM)
—Setswitch1toenableordis-
able performance monitor. To enable the PM, set the switch to
ON. To disable the PM, set the switch to OFF.
Compressor Relay Staging Operation
Switch 2 will en-
able or disable compressor relay staging operation. The com-
pressor relay can be set to turn on with stage 1 or stage 2 call
from the thermostat. This setting is used with dual stage units
(units with 2 compressors and 2 D controls) or in master/slave
applications. In master/slave applications, each compressor and
fan will stage according to its switch 2 setting. If switch is set to
stage 2, the compressor will have a 3-second delay before ener-
gizing during stage 2 demand.
NOTE: If DIP switch is set for stage 2, the alarm relay will not
cycle during Test mode.
Heating/Cooling Thermostat Type
Switch 3 provides selec-
tion of thermostat type. Heat pump or heat/cool thermostats
can be selected. Select OFF for heat/cool thermostats. When in
heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for
cooling stage 2, W1 is used for heating stage 1 and O/W2 is
used for heating stage 2. Select ON for heat pump applications.
In heat pump mode, Y1 used is for compressor stage 1, Y2 is
used for compressor stage 2, W1 is used for heating stage 3 or
emergency heat, and O/W2 is used for RV (heating or cooling)
depending upon switch 4 setting.
O/B Thermostat Type
Switch 4 provides selection for heat
pump O/B thermostats. O is cooling output. B is heating out-
put. Select ON for heat pumps with O output. Select OFF for
heat pumps with B output.
Dehumidification Fan Mode
Switch 5 provides selection
of normal or dehumidification fan mode. Select OFF for dehu-
midification mode. The fan speed relay will remain OFF dur-
ing cooling stage 2. Select ON for normal mode. The fan speed
relay will turn on during cooling stage 2 in normal mode.
Switch 6
— Not used.
Boilerless Operation
— Switch 7 provides selection of boiler-
less operation and works in conjunction with switch 8. In
boilerless operation mode, only the compressor is used for
heating when FP1 is above the boilerless changeover tempera-
ture set by switch 8 below. Select ON for normal operation or
select OFF for boilerless operation.
Boilerless Changeover Temperature
Switch 8 on S1 pro-
vides selection of boilerless changeover temperature set point.
Select OFF for set point of 10 C or select ON for set point
of 4.4 C.
If switch 8 is set for 10 C, then the compressor will be used
for heating as long as the FP1 is above 10 C. The compressor
will not be used for heating when the FP1 is below 10 C and
the compressor will operates in emergency heat mode, staging
on EH1 and EH2 to provide heat. If a thermal switch is being
used instead of the FP1 thermistor, only the compressor will be
used for heating mode when the FP1 terminals are closed. If
the FP1 terminals are open, the compressor is not used and the
control goes into emergency heat mode.
DIP SWITCH BLOCK 2 (S2) — This set of DIP switches is
used to configure accessory relay options. See Fig. 11 and 12.
Switches 1 to 3
These DIP switches provide selection
of Accessory 1 relay options. See Table 5 for DIP switch
combinations.
Switches 4 to 6
These DIP switches provide selection
of Accessory 2 relay options. See Table 6 for DIP switch
combinations.
IMPORTANT: Jumpers and DIP switches should only
be clipped when power to control board has been turned
off.