c. On all units remove blower assembly from unit. Remove
screws securing blower to blower partition and slide
assembly out. Be careful not to tear insulation in blower
compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
remove screws that secure motor mount brackets to hous-
ing, and slide motor and motor mount out of housing.
2. Remove and clean blower wheel as follows:
a. Ensure proper reassembly by marking wheel orientation.
b. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights (clips)
on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush attach-
ment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrews are
tightened on motor shaft flats and not on round part of
shaft.
f. Reinstall unit access panel.
3. Restore electrical power to unit. Start unit and check for
proper blower rotation and motor speeds during heating and
cooling cycles.
°
(030) 60HZ CHARGING CHART
OUTDOOR TEMP
° F ° C
115 46
45 7
55 13
65 18
75 24
95 35
105 41
85 29
C99046
Fig. 23—Cooling Charging Chart, 50GX030 Units
Fig. 25—Cooling Charging Chart, 50GX042 Units
C99047
°
OUTDOOR TEMP
° F ° C
115 46
45 7
55 13
65 18
75 24
95 35
105 41
85 29
(042) 60HZ CHARGING CHART
°
OUTDOOR TEMP
° F ° C
115 46
45 7
55 13
65 18
75 24
95 35
105 41
85 29
(036) 60HZ CHARGING CHART
C99045
Fig. 24—Cooling Charging Chart, 50GX036 Units
°
OUTDOOR TEMP
° F ° C
115 46
45 7
55 13
65 18
75 24
95 35
105 41
85 29
(048) 60HZ CHARGING CHART
C99048
Fig. 26—Cooling Charging Chart, 50GX048 Units
23