Carrier 48HJD005-007 Air Conditioner User Manual


 
45
LEGEND AND NOTES FOR FIG. 55
AHA
Adjustable Heat Anticipator
C
Contactor, Compressor
CAP
Capacitor
CC
Cooling Compensator
CLO
Compressor Lockout
COMP
Compressor Motor
D
Diode
EC
Enthalpy Control
ECON
Economizer
EPS
Emergency Power Supply
EQUIP
Equipment
ER
Economizer Relay
FPT
Freeze-Protection Thermostat
FSS
Filter-Status Switch
FU
Fuse
GND
Ground
GVR
Gas Valve Relay
HPS
High-Pressure Switch
HS
Hall-Effect Sensor
HV
High Voltage
I
Ignitor
IDM
Induced-Draft Motor
IFC
Indoor (Evaporator) Fan Contactor
IFM
Indoor (Evaporator) Fan Motor
IGC
Integrated Gas Unit Controller
LED
Light-Emitting Diode
LPS
Low-Pressure/Loss-of-Charge Switch
LS
Limit Switch
MGV
Main Gas Valve
MTR
Motor
OAT
Outdoor-Air Thermostat
OFM
Outdoor (Condenser) Fan Motor
P
Plug
PL
Plug Assembly
QT
Quadruple Terminal
R
Relay
RS
Rollout Switch
SAT
Supply-Air Thermostat
SEN
Sensor
SW1
Switch Fully Open
SW2
Switch Fully Closed
SW3
Switch Minimum Vent Position
SW4
Switch Maximum Vent Position
TC
Thermostat-Cooling
TH
Thermostat-Heating
TRAN
Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
NOTES FOR FIG. 55
1. If any of the original wire furnished must be replaced, it must be replaced with Type 90 C wire or its
equivalent.
2. Three-phase motors are protected under primary single-phasing conditions.
3. Thermostats: HH07AT170, 172
Subbase: HH93AZ176, 177, 178 and 179
4. Set heat anticipator at .14 amp for first stage and .14 amp for second stage.
5. Use copper conductors only.
6. TRAN is wired for 230 v unit. If unit is to be run with 208 v power supply, disconnect BLK wire from
230 v tap and connect to 208 v tap (RED). Insulate end of 230 v tap.