Table 14 48HJ006 Fan Performance Vertical Discharge Units With Standard Motor
Single-Phase Units
3-Phase Units
Table 15 48HJ006 Fan Performance Vertical Discharge Units With High-Static Motor
LEGEND AND NOTES FOR TABLES 14 AND 15
L
EGEND
NOTES:
1. Boldface indicates field-supplied drive required. (See Note 3.)
2. indicates field-supplied motor and drive required.
3. Motor drive range is 1020 to 1460 rpm for single-phase standard
motors, 1120 to 1585 for 3-phase standard motors, and 1300 to 1685 for
high-static motors. All other rpms require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils. See page 28
for accessory/FIOP static pressure information.
5. Maximum continuous bhp is 1.30 for single-phase standard motors, 2.40
for 3-phase standard motors, and 2.90 for high-static motors. Extensive
motor and electrical testing on these units ensures that the full range of
the motor can be utilized with confidence. Using your fan motors up to
the ratings shown will not result in nuisance tripping or premature motor
failure. Unit warranty will not be affected. See Evaporator-Fan Motor
Data tables on page 20 for additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 771 0.37 828 0.44 935 0.58 1027 0.73 1107 0.88 1185 1.04 1257 1.20
1330 1.38 1411 1.59
1600 816 0.45 869 0.51 968 0.66 1056 0.81 1127 0.97 1215 1.14
1286 1.31 1353 1.49 1421 1.68
1700 902 0.61 940 0.60 1007 0.75 1094 0.91 1175 1.09 1245 1.26
1315 1.44 1381 1.52 1443 1.69
1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20
1322 1.33 1395 1.46 1475 1.56 1542 1.71
1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29
1356 1.47 1430 1.58 1504 1.69 1556 1.82
2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23
1303 1.41 1397 1.52 1459 1.67 1532 1.82 1588 1.97
2100 1063 0.99 1115 1.00 1180 1.17
1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 1626 2.16
2200 1104 1.13 1159 1.15 1214 1.28
1310 1.52 1375 1.63 1459 1.80 1528 1.95 1603 2.17 1666 2.37
2300 1130 1.26 1202 1.29
1248 1.38 1358 1.69 1410 1.72 1488 1.93 1561 2.13 1637 2.35 1710 2.54
2400
1174 1.37 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1584 2.28 1671 2.55 1756 2.70
2500
1201 1.48 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35 1633 2.53 1698 2.72 ——
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 771 0.37 828 0.44 935 0.58 1027 0.73 1107 0.88 1185 1.04 1257 1.20 1330 1.38 1411 1.59
1600 816 0.45 869 0.51 968 0.66 1056 0.81 1127 0.97 1215 1.14 1286 1.31 1353 1.49 1421 1.68
1700 902 0.61 940 0.60 1007 0.75 1094 0.91 1175 1.09 1245 1.26 1315 1.44 1381 1.52 1443 1.69
1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20 1322 1.33 1395 1.46 1475 1.56 1542 1.71
1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29 1356 1.47 1430 1.58 1504 1.69 1556 1.82
2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23 1303 1.41 1397 1.52 1459 1.67 1532 1.82 1588 1.97
2100 1063 0.99 1115 1.00 1180 1.17 1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 1626 2.16
2200 1104 1.13 1159 1.15 1214 1.28 1310 1.52 1375 1.63 1459 1.80 1528 1.95 1603 2.17 1666 2.37
2300 1130 1.26 1202 1.29 1248 1.38 1358 1.69 1410 1.72 1488 1.93 1561 2.13 1637 2.35
1710 2.54
2400 1174 1.37 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1584 2.28
1671 2.55 1756 2.70
2500 1201 1.48 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35
1633 2.53 1698 2.72 ——
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 808 0.42 914 0.56 1001 0.69 1084 0.85 1168 1.01
1600 846 0.49 950 0.64 1034 0.78 1111 0.94 1194 1.11
1700 884 0.57 983 0.72 1068 0.88 1145 1.03 1218 1.21
1800 924 0.66 1018 0.82 1105 0.98 1179 1.13 1246 1.32
1900 965 0.76 1057 0.92 1143 1.10 1212 1.26 1280 1.43
2000 1008 0.87 1096 1.04 1177 1.22 1247 1.40 1300 1.57
2100 1051 0.99 1136 1.17 1210 1.35 1284 1.54 1347 1.72
2200 1095 1.12 1173 1.30 1245 1.49 1322 1.70 1380 1.89
2300 1140 1.26 1210 1.47 1284 1.65 1356 1.80 1418 2.07
2400 1185 1.41 1249 1.61 1323 1.80 1389 2.03 1456 2.26
2500 1231 1.57 1289 1.78 1363 2.00 1424 2.22 1500 2.45
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1500 1199 1.19 1126 1.46 1250 1.69 1301 1.91 1349 2.12
1600 1263 1.28 1275 1.49 1299 1.78 1352 2.01 1401 2.23
1700 1295 1.39 1351 1.58 1352 1.80 1407 2.03 1459 2.26
1800 1319 1.52 1389 1.71 1435 1.91 1494 2.15 1548 2.40
1900 1343 1.64 1415 1.80 1478 2.05 1538 2.31 1594 2.57
2000 1374 1.77 1438 1.99 1505 2.21 1566 2.49 1624 2.77
2100 1409 1.91 1465 2.14 1533 2.45 1596 2.77
1654 3.08
2200 1442 2.08 1498 2.30 1568 2.64
1632 2.97 1691 3.31
2300 1475 2.26 1554 2.64
1627 3.03 1693 3.42 1755 3.81
2400 1565 2.47 1649 2.89
1726 3.31 ————
2500
1596 2.95 1682 3.45 1760 3.96 ————
Bhp Brake Horsepower Input to Fan
FIOP Factory-Installed Option