25
BROADCAST CONFIGURATION SUB-MENU
ITEM # FORMAT COMMENTS
0 broAdCASt MEnu When selected this item authorises a return to the main menu.
1 YES/no Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network. There must be
only one broadcast acknowledger in a CCN.
Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used
(see section 4.5.7.8) or if you want to configure the daylight saving time function.
2 YES/no This item authorises enabling or disabling the Broadcast function. When it is set to Yes, the control will make a periodic
broadcast on the CCN. When it is set to No, the control is not the broadcaster and there is no need to configure the other choice in
this table. There must be only one broadcaster in a CCN and this item should not be configured if any other system element is
acting as broadcaster.
Warning: if the unit operates in standalone (not CCN connected) this choice must be set to Yes if the holiday function is used (see
section 4.5.7.8) or if you want to configure the daylight saving time function.
3 nnn OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.
0 to 239 Used for CCN network function only.
4 nnn OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor
0 to 239 connected to it. Used for CCN network function only.
5nn Daylight saving start month. In this mode you enter the month in which the broadcaster will adjust its time for the start of
1 to 12 daylight saving time.
6nn Daylight saving start day. In this mode you enter the day on which the broadcaster will adjust its time for the start of daylight
1 to 31 saving time.
7n
1
n
2
n
3
n
4
Authorises entering the hours and minutes for saving start. In this mode you enter the time of day when the broadcaster will
00:00 to 24:00 adjust its time for the start of daylight saving time.
n
1
n
2
: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so
that hours can be adjusted.
n
3
n
4
: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be
adjusted.
8 nnnn Daylight saving start minutes to add: number of minutes by which the broadcaster will adjust its time for the start of daylight
1 to 1440 minutes saving time.
9nn Daylight saving stop month. In this mode you enter the month in which the broadcaster will adjust its time for the end of
1 to 12 daylight saving time.
10 nn Daylight saving stop day. In this mode you enter the day on which the broadcaster will adjust its time for the end of daylight
1 to 31 saving time.
11 n
1
n
2
n
3
n
4
Authorises entering the hours and minutes for saving stop. In this mode you enter the time of day when the broadcaster
00:00 to 24:00 will adjust its time for the end of daylight saving time.
12 nnnn Daylight saving start minutes to subtract: number of minutes by which the broadcaster will adjust its time for the end of
1 to 1440 minutes daylight saving time.
n
1
n
2
: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.
n
3
n
4
: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.
4.5.8 - Description of the Alarms menu
This menu is used to display and reset up to 5 active alarms. It
also permits alarm reset. If no alarm is active this menu is not
accessible. See section 6 for a complete description of the
alarm codes and alarm reset.
ALARMS MENU
ITEM # FORMAT DESCRIPTION
0 [1] X ALArM X alarms are active
rESEt ALArM Reset of alarms is requested
To reset all active alarms, continuously press the Enter
key. ‘rESET ALArM’ is then displayed. Press the select
key again: all alarms are reset.
1 [1] nn Current alarm code 1*
2 [1] nn Current alarm code 2*
3 [1] nn Current alarm code 3*
4 [1] nn Current alarm code 4*
5 [1] nn Current alarm code 5*
Legend
1 This item is masked when nil
* Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
“time of alarm” “date of alarm” “full CCN alarm message”
- “time of alarm”: hh-mm
- “date”: dd-mm
- “full CCN alarm message”: up to 64 characters
4.5.9 - Description of the Alarms History menu
ALARMS HISTORY MENU
ITEM # FORMAT COMMENTS
1 [1] nn Alarm history code 1*
2 [1] nn Alarm history code 2*
3 [1] nn Alarm history code 3*
4 [1] nn Alarm history code 4*
5 [1] nn Alarm history code 5*
6 [1] nn Alarm history code 6*
7 [1] nn Alarm history code 7*
8 [1] nn Alarm history code 8*
9 [1] nn Alarm history code 9*
10 [1] nn Alarm history code 10*
Legend
1 This item is masked when nil
* Pressing the Enter key when alarm code is displayed causes the following
message to be scrolled:
“time of alarm” “date of alarm” “full CCN alarm message”
- “time of alarm”: hh-mm
- “date”: dd-mm
- “full CCN alarm message”: up to 64 characters