20
4.5.6.3 - Manual tests
This function allows the user to test the outputs individually, if
the machine is completely shut down (LOFF). To carry out a
manual test use the arrow keys to access the output to be tested
and press the Enter key (longer than 2 seconds) to activate the
modification mode. The password is automatically requested, if it
has not previously been verified. The Outputs/Test LED on the
user interface begins to flash. Enter the desired test value and
again press Enter to start the test. 'TESt' is displayed on the 4-
digit display alternately with the value tested. The Outputs/Test
LED stops flashing. Press the Enter key or an arrow key to stop
the test.
4.5.7 - Description of the Configuration menu
4.5.7.1- General
This menu can be used to display and modify all configura-
tions: Factory, Service and User. Only the User Configuration
can be modified by the end-user. The Factory, Service and
master/slave configurations are not described in this docu-
ment. A configuration can only be modified if the unit is fully
stopped (LOFF).
The menus User 1 [USEr 1] and User 2 [USEr 2] are pass-
word-protected. The other menus are directly accessible, except
if item 12 of the User 1 menu (password for all configurations)
has been validated.
4.5.7.2 - Password
A password must be entered in order to access the test function
or to modify a configuration. It is automatically requested, if
necessary: 'EntEr PASS' is displayed on the 4-digit display and
the configuration menu LED flashes, indicating that the modifi-
cation mode is active. Press the arrow keys until the value '11'
is displayed on the 4-digit display. Press Enter to validate this.
The configuration menu LED stops flashing. If the password is
correct, 'Good' is displayed. If the password is incorrect, 'PASS
incorrEct' is displayed. The User password has a default value
of 11.
This value can be modified through the Service configuration.
The password can be entered if the unit is fully stopped, other-
wise 'ACCES dEniEd' (access denied) will be displayed on the
4-digit display. The controller automatically deactivates the
password after 5 minutes without activity (i.e. no buttons
pressed) or after powering up.
SUB-MENU USER CONFIGURATION
SCHEDULE 1
[ScHEduLE 1MEnu]*
Return to previous menu
SUB-MENU:
Period 1 [PErIod 1]
SUB-MENU:
Period 2 [PErIod 2]
SUB-MENU:
Period 3 [PErIod 3]
SUB-MENU:
Period 4 [PErIod 4]
SUB-MENU:
Period 5 [PErIod 5]
SUB-MENU:
Period 6 [PErIod 6]
SUB-MENU:
Period 7 [PErIod 7]
SUB-MENU:
Period 8 [PErIod 8]
-
-
-
-
-
-
-
-
DATE
[dAtE]*
Return to previous
menu
Hour*
Day of the week*
Day and month*
Year*
-
-
-
-
-
-
-
-
-
-
-
-
SCHEDULE 2
[ScHEduLE 2 MEnu]*
Return to previous
menu
SUB-MENU:
Period 1 [PErIod 1]
SUB-MENU:
Period 2 [PErIod 2]
SUB-MENU:
Period 3 [PErIod 3]
SUB-MENU:
Period 4 [PErIod 4]
SUB-MENU:
Period 5 [PErIod 5]
SUB-MENU:
Period 6 [PErIod 6]
SUB-MENU:
Period 7 [PErIod 7]
SUB-MENU:
Period 8 [PErIod 8]
-
-
-
-
-
-
-
-
HOLIDAYS
[HOLidAy MEnu]*
Return to previous menu
SUB-MENU:
Holidays 1 [HOLidAy 1]
SUB-MENU:
Holidays 2 [HOLidAy 2]
SUB-MENU:
Holidays 3 [HOLidAy 3]
SUB-MENU:
Holidays 4 [HOLidAy 4]
SUB-MENU:
Holidays 5 [HOLidAy 5]
SUB-MENU:
Holidays 6 [HOLidAy 6]
SUB-MENU:
Holidays 7 [HOLidAy 7]
SUB-MENU:
Holidays 8 [HOLidAy 8]
SUB-MENU:
Holidays 9 [HOLidAy 9]
SUB-MENU:
Holidays 10 [HOLidAy 10]
SUB-MENU:
Holidays 11 [HOLidAy 11]
SUB-MENU:
Holidays 12 [HOLidAy 12]
SUB-MENU:
Holidays 13 [HOLidAy 13]
SUB-MENU:
Holidays 14 [HOLidAy 14]
SUB-MENU:
Holidays 15 [HOLidAy 15]
SUB-MENU:
Holidays 16 [HOLidAy 16]
BROADCAST
[BrodCASt]*
Return to previous menu
Broadcast acknowledger
selection
Broadcast activation
Outdoor temperature
broadcast bus
Outdoor temperature
broadcast element
Start month daylight
saving time
Start day daylight saving
time
Start hour daylight saving
time
Minutes to add
End month daylight saving
time
End day daylight saving
time
End hour daylight saving
time
Minutes to subtract
-
-
-
-
USER 2
[USER2]*
Return to previous
menu*
Periodic pump start-
up*
Night mode - start
hour*
Night mode - end
hour*
Night mode - demand
limit in %
Number clock 1*
Number clock 2*
CCN address *
CCN bus*
-
-
-
-
-
-
-
-
USER 1
[USER1]
Return to previous menu
Circuit selection
Circuit capacity increase
sequence
Ramp selection*
Start-up delay*
Water pump selection
Water pump changover
delay*
Automatic reset
selection*
Demand limit selection
Voltage corresponding to
100% of demand limit
Voltage corresponding to
0% of demand limit
Extended display
selection
Password for all user
configurations
Software version number
-
-
-
ITEM
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Legend:
*: only displayed if configuration requires.