APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION
CCN
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
System Cooling Demand
Level
N/A R N/A N/A N/A AV:9006 cool_demand_level_1
System Demand Limiting N/A R N/A N/A OFF/ON BV:3 dem_lmt_act_1
Target Guide Vane Position GV_TRG R % N/A 0 to 100 AV:41 gv_trg_1
Target VFD Speed VFD_OUT R % N/A 0 to 100 AV:42 vfd_out_1
Tower Fan Relay High TFR_HIGH R N/A OFF OFF/ON BV:13 tfr_high_1
Tower Fan Relay Low TFR_LOW R N/A OFF OFF/ON BV:14 tfr_low_1
User Defined Analog 1 N/A R N/A N/A N/A AV:2901 user_analog_1_1
User Defined Analog 2 N/A R N/A N/A N/A AV:2902 user_analog_2_1
User Defined Analog 3 N/A R N/A N/A N/A AV:2903 user_analog_3_1
User Defined Analog 4 N/A R N/A N/A N/A AV:2904 user_analog_4_1
User Defined Analog 5 N/A R N/A N/A N/A AV:2905 user_analog_5_1
User Defined Binary 1 N/A R N/A N/A N/A BV:2911 user_binary_1_1
User Defined Binary 2 N/A R N/A N/A N/A BV:2912 user_binary_2_1
User Defined Binary 3 N/A R N/A N/A N/A BV:2913 user_binary_3_1
User Defined Binary 4 N/A R N/A N/A N/A BV:2914 user_binary_4_1
User Defined Binary 5 N/A R N/A N/A N/A BV:2915 user_binary_5_1
CHW Chilled Water
R—Read
VFD Variable Frequency Drive
W—Write