10
LEGEND
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, and
480 v. Heaters are rated at 240 v, or 480 v. If power distribution volt-
age to unit varies from rated heater voltage, heater kW will vary
accordingly.
Fuse or HACR circuit breaker.
**Heaters are field installed only.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. MCA calculation for units with electric heaters over 50 kW = (1.25 x
IFM amps) + (1.00 x heater FLA).
Table 3 — Electric Resistance Heater Data
*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-ambient kit.
NOTE:
Heaters are rated at 240, and 480 v.
FLA
Full Load Amps
HACR—
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP—
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
7
457
UNIT
551A
HEATER kW
HEATER
STAGES
% HEAT
PER
STAGE
MAXIMUM
STAGES*
MINIMUM
HEATER AMPS
Unit Voltages Heating Cfm
208 230 240 460 480 Cfm L/s 208 230 240 460 480
155
14 17 19 14 15 1 100 1
3750 1770
39.3 43.4 45.3 17.2 17.9
26 31 34 30 32 2 50/50 2 71.3 78.9 82.3 37.3 39.0
42 52 56 50 55 2 33/67 3 117.0 129.4 135.0 63.3 66.1
180
26 31 34 30 32 2 50/50 2
3750 1770
71.3 78.8 82.3 37.3 39.0
42 52 56 50 55 2 33/67 3 117.0 129.4 135.0 63.3 66.1
56 69 75 73 80 2 50/50 4 155.9 172.4 179.9 92.0 96.0
240
26 31 34 30 32 2 50/50 2
5000 2360
71.3 78.8 82.3 37.3 39.0
42 52 56 50 55 2 33/67 3 117.0 129.4 135.0 63.3 66.1
56 69 75 73 80 2 50/50 4 155.9 172.4 179.9 92.0 96.0