Bryant 120 Furnace User Manual


 
26
ACCESSORIES
1. Electronic Air Cleaner (EAC)
Connect an accessory Electronic Air Cleaner (if used)
using 1/4--in female quick connect terminals to the two
male 1/4--in quick--connect terminals on the control board
marked EAC--1 and EAC--2. The terminals are rated for
115VAC, 1.0 amps maximum and are energized during
blower motor operation. (See Fig. 34.)
2. Humidifier (HUM)
Connect an accessory 24 VAC, 0.5 amp. maximum
humidifer (if used) to the 1/4--in male quick--connect
HUM terminal and COM--24V screw terminal on the
control board thermostat strip. The HUM terminal is
energized when gas valve relay (GVR) is energized. (See
Fig. 34.)
NOTE: A field--supplied, 115--v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
NOTE: DO NOT connect furnace control HUM terminal to
HUM (humidifier) terminal on Thermidistat, Zone Controller or
similar device. See Thermidistatt, Zone Controller, thermostat,
or controller manufacturer’s instructions for proper connection.
VENTING
The furnace shall be connected to a listed factory built chimney
or vent or a clay--tile lined masonry or concrete chimney. Venting
into an unlined masonry chimney or concrete chimney is
prohibited. When an existing Category I furnace is removed or
replaced, the original venting system may no longer be sized to
properly vent the attached appliances. An improperly sized
Category I venting system could cause the formation of
condensate in the furnace and vent, leakage of condensate and
combustion products, and spillage of combustion products into
the living space.
LHT
OFF
DLY
ON
OFF
W2
BLW
24-V-THERMOSTAT
TERMINALS
SETUP SWITCHES
LOW-HEAT ONLY AND
BLOWER OFF-DELAY
TWINNING AND/OR
COMPONENT TEST
TERMINAL
ACRDJ - AIR CONDITIONING
RELAY DISABLE JUMPER
TRANSFORMER 24-VAC
CONNECTIONS
PL1 - LOW VOLTAGE MAIN
HARNESS CONNECTOR
PL3
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
3-AMP FUSE
LED OPERATION &
DIAGNOSTIC LIGHT
115-VAC (L2) NEUTRAL
CONNECTIONS
PL2 - HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
115-VAC (L1) LINE
VOLTAGE CONNECTION
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
BLOWER SPEED
SELECTION TERMINALS
HI HEAT
LO HEAT
SPARE-1
SPARE-2
COOL
Y1 DHUM G COM
24V
WW1 Y/Y2 R
TEST/TWIN
HUM
1 2 3
PLT
ACRDJ
0.5-AMP024 VAC
FUSE 3-AMP
SEC-1 SEC-2
PL1
NEUTRAL-L2
1
EAC-2
BHT/CLRBHI/LOR
PL3 1
BLWR
COOL
SPARE-1 SPARE-2
1-AMP@115 VAC
EAC-1 PR-1
IDR
HSIR
IDM
IHI/LOR
PL2
1
HSI HI LO
S
T
A
T
U
S
C
O
D
E
L
E
D
HI HEAT LO HEAT
L1
A02017
Fig. 34 -- Furnace Control--PSC Blower Motor
312A