230 and 230/208 volt models
with amperes up through 24.0
Receptacle wiring
Receptacle wiring should be a minimum of
IO gauge. Use copper wire only. It is the
responsibility of the consumer to provide
proper and adequate receptacle wiring,
installed by a qualified electrician. Observe
National Electrical Code and all local governing
codes and ordinances.
Electrical requirements
A 230 volt (207 min., 253 max.), 60 Hz, AC only,
30 ampere (cartridge type) fused electrical supply
is required (time delay fuse or time delay circuit
breaker required). It is required that a separate
circuit, serving only this appliance, be provided.
OR
A 230/208 volt (197.6 min., 253 max.), 60 Hz,
AC only, 30 ampere (cartridge type) fused
electrical supply is required (time delay fuse or
time delay circuit breaker required). It is required
that a separate circuit, serving only this appli-
ance, be provided.
Electrical connection
3-prong
grounding
h/pe wall
receptacle
Electrical ground is required on this appliance.
Recommended grounding method
For your personal safety, this appliance must be
grounded. This air conditioner is equipped with a
power supply cord having a 3-prong grounding
3-prong
plug. To minimize possible shock hazard, the
cord must be plugged into a mating 3-prong
grounding-type wall receptacle, grounded in
accordance with the National Electrical Code
(ANSVNFPA 70-lastest edition) and local codes
and ordinances. If a mating wall receptacle is not
available, it is the responsibility of the customer to
have a properly grounded 3-prong wall receptacle
installed by a qualified electrician.
7