Whirlpool ACC602XP0 Air Conditioner User Manual


 
Electrical Requirements
Continued
230 and 230/208 volt models
with amperes up through 16.0
Receptacle wiring
Receptacle wiring should be a minimum of
12 gauge. Use copper wire only. It is the
responsibility of the consumer to provide
proper and adequate receptacle wiring,
installed by a qualified electrician. Observe
National Electrical Code and all local governing
codes and ordinances.
Electrical requirements
A 230 volt (207 min., 253 max.), 60 Hz, AC only,
20 ampere fused electrical supply is required
(time delay fuse or time delay circuit breaker
required). It is required that a separate circuit,
serving only this appliance, be provided.
OR
A 230/208 volt (197.6 min., 253 max.), 60 Hz,
AC only, 20 ampere fused electrical supply is
required (time delay fuse or time delay circuit
breaker required). It is required that a separate
circuit, serving only this appliance, be provided.
Electrical connection
Power
3-prong
grounding
type wall
Electrical ground is required on this appliance.
Recommended grounding method
For your personal safety, this appliance must be
grounded. This air conditioner is equipped with a
power supply cord having a 3-prong grounding
plug. To minimize possible shock hazard, the
cord must be plugged into a mating 3-prong
grounding-type wall receptacle, grounded in
accordance with the National Electrical Code
(ANSIINFPA 70-latest edition) and local codes
and ordinances. If a mating wall receptacle is not
available, it is the responsibility of the customer to
have a properly grounded 3-prong wall receptacle
installed by a qualified electrician.