Trane YSC060-120 Air Conditioner User Manual


 
37RT-PRC017-EN
Performance
Data
Table PD-24 - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Downflow Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Low Static Drive 2.24 Nom kW Standard
Motor & Drive
5440 - - - - 723 0.74 759 0.84 793 0.94 827 1.05 860 1.15 891 1.26 921 1.37 949 1.49
6120 721 0.78 755 0.87 787 0.96 820 1.07 851 1.18 882 1.30 913 1.42 942 1.54 971 1.66 999 1.78
6800 793 1.04 824 1.15 854 1.25 883 1.36 913 1.48 941 1.60 969 1.73 997 1.86 1024 1.99 1050 2.12
7480 866 1.36 895 1.48 923 1.59 949 1.70 976 1.83 1003 1.96 1029 2.10 1054 2.24 1079 2.38 1104 2.53
8160 939 1.75 967 1.87 992 1.99 1017 2.12 1042 2.24 1066 2.38 1090 2.52 1114 2.67 1138 2.83 1161 2.98
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Drive
5440 976 1.61 1001 1.73 1027 1.86 1051 1.99 1075 2.12 1098 2.25 1120 2.38 1143 2.52 1166 2.66 1189 3.59
6120 1025 1.90 1052 2.03 1076 2.17 1100 2.30 1122 2.44 1145 2.58 1167 2.73 1188 2.87 1210 3.02 1230 4.02
6800 1076 2.26 1101 2.39 1126 2.53 1149 2.67 1172 2.81 1194 2.96 1216 3.12 1236 3.26 - - - -
7480 1129 2.67 1153 2.81 1176 2.96 1200 3.11 1222 3.26 - - --------
8160 1184 3.14 1207 3.30 - - - - - - - - --------
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-24a - Belt Drive Evaporator Fan Performance - YSC120AD*H - High Heat - Downflow Configuration - (IP)
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Low Static Drive 3 HP Standard Motor & Drive
3200 - - - - 723 0.99 759 1.12 793 1.26 827 1.40 860 1.55 891 1.69 921 1.84 949 2.00
3600 721 1.04 755 1.17 787 1.29 820 1.44 851 1.59 882 1.75 913 1.90 942 2.06 971 2.22 999 2.39
4000 793 1.40 824 1.54 854 1.67 883 1.82 913 1.98 941 2.15 969 2.32 997 2.50 1024 2.67 1050 2.85
4400 866 1.83 895 1.98 923 2.13 949 2.28 976 2.45 1003 2.63 1029 2.81 1054 3.00 1079 3.20 1104 3.39
4800 939 2.34 967 2.51 992 2.67 1017 2.84 1042 3.01 1066 3.19 1090 3.38 1114 3.58 1138 3.79 1161 4.00
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive
3200 976 2.16 1001 2.32 1027 2.49 1051 2.66 1075 2.84 1098 3.02 1120 3.19 1143 3.38 1166 3.57 1189 3.75
3600 1025 2.55 1052 2.73 1076 2.90 1100 3.09 1122 3.27 1145 3.46 1167 3.66 1188 3.85 1210 4.05 1230 4.25
4000 1076 3.03 1101 3.20 1126 3.40 1149 3.58 1172 3.77 1194 3.97 1216 4.18 1236 4.38 - - - -
4400 1129 3.58 1153 3.77 1176 3.97 1200 4.17 1222 4.37 - - --------
4800 1184 4.21 1207 4.42 - - - - - - - - --------
3 HP Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.