Trane YSC060-120 Air Conditioner User Manual


 
13RT-PRC017-EN
General Data
T
able GD-1 — General Data
Convertible Units Convertible Units Convertible Units Convertible Units Convertible Units
YSC060AD YSC072AD YSC090AD YSC102AD YSC120AD
Cooling Performance
1
Gross Capacity - kW (MBh) 18.2 (62.0) 23.2 (79.0) 26.7 (91.0) 31.1 (106.0) 34.9 (119.0)
COP (EER)
2
2.99 (10.2) 3.08 (10.5) 3.02 (10.3) 3.02 (10.3) 2.99 (10.2)
Nominal Airflow - m
3
/h (cfm) 3400 (2000) 4080 (2400) 5100 (3000) 5780 (3400) 6800 (4000)
Rated Airflow - m
3
/h (cfm) 3400 (2000) 3570 (2100) 4460 (2625) 5100 (3000) 5950 (3500)
Net Capacity - kW (MBh) 17.3 (59.0) 22.0 (75.0) 25.2 (86.0) 29.9 (102.0) 33.1 (113.0)
System Power - kW 5.78 7.14 8.35 9.9 11.08
Heating Performance
3
Heating Models Low - G80 High - G120 Low - G120 High G-200 Low - G120 High G-200 Low - G150 High G-250 Low - G150 High G-250
Heating Input - kW (MBH) 19.6 (67) 29.3 (100) 29.3 (100) 48.9 (167) 29.3 (100) 48.9 (167) 36.7 (125) 60.9 (208) 36.7 (125) 60.9 (208)
Heating Output - kW (MBH) 15.7 (54) 23.4 (80) 23.4 (80) 39.1 (134) 23.4 (80) 39.1 (134) 29.3 (100) 48.7 (166) 29.3 (100) 48.7 (166)
Steady State Efficiency % 90 90 90 90 90 90 90 90 90 90
No. Burners 2 3 3 4 3 4 3 5 3 5
No. Stages 1 1 1 2 1 2 2 2 2 2
Gas Connection Pipe Size - in. 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT 3/4 NPT
Compressor
Number - Type 1-Climatuff Scroll 1-Trane 3-D Scroll 1-Trane 3-D Scroll 2-Climatuff Scroll 2-Climatuff Scroll
Outdoor Sound Rating dB
4
80 85 85 83 79
Outdoor Coil - Type Lanced Lanced Lanced Lanced Lanced
Tube Size in. OD 0.3125 0.3125 0.3125 0.3125 0.3125
Face Area - m
2
(sq ft) 1.02 (10.96) 1.29 (13.88) 1.29 (13.88) 1.75 (18.89) 2.41 (25.92)
Rows / FPI 3 / 17 2 / 17 2 / 17 2 / 17 2 / 17
Indoor Coil - Type Lanced Lanced Lanced Lanced Lanced
Tube Size OD - in. 0.3125 0.3125 0.3125 0.3125 0.3125
Face Area - m
2
(sq ft) 0.62 (6.68) 0.92 (9.89) 0.92 (9.89) 1.15 (12.36) 1.15 (12.36)
Rows / FPI 3 / 16 2 / 16 3 / 16 3 / 16 4 / 16
Refrigerant Control Short Orifice Short Orifice Short Orifice Short Orifice Short Orifice
Drain Connection No. / Size - in. 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT 1 / 0.75 NPT
Outdoor Fan - Type Propeller Propeller Propeller Propeller Propeller
No. Used / Diameter - in. 1 / 22 1 / 26 1 / 26 1 / 26 1 / 26
Drive Type / No. Speeds Direct / 1 Direct / 1 Direct / 1 Direct / 1 Direct / 1
CFM 2900 5100 5200 5500 5800
No. Motors / kW (HP) 1 / 0.30 (0.40) 1 / .56 (0.75) 1 / .56 (0.75) 1 / .56 (0.75) 1 / .56 (0.75)
Motor RPM 950 950 950 950 950
Belt Drive Indoor Fan - Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1 1
Fan Diameter x Width - mm (in.) 280 X 280 (11 x 11) 305 X 305 (12 x 12) 305 X 305 (12 x 12) 381 X 381 (15 x 15) 381 X 381 (15 x 15)
Drvie Type / No. Speeds Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed Belt / Variable Speed
No. Motors 1 1 1 1 1
Standard Motor Power - kW (HP) 1.1 (1.5) 1.1 (1.5) 1.5 (2.0) 1.5 (2.0) 2.2 (3.0)
Oversized Motor Power - kW (HP) - 1.5 (2.0) 2.2 (3.0) 2.2 (3.0) -
Motor RPM - Standard / Oversized 1450 / - 1450 / 1450 1450 / 2850 1450 / 2850 2850 / -
Motor Frame Size 56 56 56 56 56
Filters - Type Furnished Throwaway Throwaway Throwaway Throwaway Throwaway
(No.) Size Reccommended - mm (2) 508 X 762 X 25 (4) 406 X 635 X 50 (4) 406 X 635 X 50 (4) 508 X 635 X 50 (4) 508 X 635 X 50
(No.) Size Reccommended - in. (2) 20 X 30 X 1 (4) 16 X 25 X 2 (4) 16 X 25 X 2 (4) 20 X 25 X 2 (4) 20 X 25 X 2
Refrigerant Charge - kg (lbs) of R-22
5
3.7 (8.2) 3.7 (8.2) 4.5 (10.0) Circuit 1 - 3.8 (8.3) Circuit 1 - 3.4 (7.5)
Circuit 2 - 2.0 (4.4) Circuit 2 - 3.3 (7.3)
Notes:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor
heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ± 20 % of nominal airflow.
2. EER are rated at ARI conditions.
3. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level".
5. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.