Trane YSC060-120 Air Conditioner User Manual


 
RT-PRC017-EN32
Performance
Data
Table PD-19 - Belt Drive Evaporator Fan Performance - YSC102AD*L - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4620 610 0.44 657 0.52 700 0.60 747 0.70 793 0.80 837 0.91 873 1.00 905 1.09 935 1.18 963 1.27
5200 675 0.61 718 0.70 757 0.78 794 0.87 837 0.98 879 1.10 919 1.22 955 1.34 987 1.44 1014 1.54
5780 742 0.82 779 0.91 817 1.01 851 1.10 885 1.21 923 1.33 962 1.46 999 1.59 1033 1.72 1066 1.85
6350 810 1.07 842 1.16 878 1.27 911 1.38 941 1.49 972 1.60 1006 1.73 1041 1.87 1076 2.02 1109 2.17
6930 878 1.37 907 1.47 939 1.58 971 1.70 1000 1.82 1029 1.94 1056 2.06 1087 2.20 1120 2.35 1151 2.50
2.24 Nom kW Over-Sized Motor & High Static Drive
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Drive
4620 989 1.36 1015 1.45 1038 1.53 1062 1.62 1085 1.71 1108 1.80 1129 1.88 1152 1.98 1172 2.06 1194 2.16
5200 1042 1.64 1067 1.74 1092 1.84 1115 1.94 1138 2.04 1159 2.14 1180 2.23 1200 2.33 1221 2.43 1241 2.53
5780 1093 1.97 1118 2.08 1144 2.19 1167 2.30 1190 2.41 1212 2.52 1233 2.63 1253 2.74 1273 2.85 1292 2.96
6350 1140 2.31 1169 2.45 1195 2.58 1219 2.70 1242 2.83 1264 2.95 1286 3.07 1307 3.19 1326 3.31 - -
6930 1182 2.66 1213 2.83 1241 2.98 1268 3.14 1292 3.28 - - --------
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-19a - Belt Drive Evaporator Fan Performance - YSC102AD*L - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Low Static Drive 2 HP Standard Motor & Drive
2720 610 0.59 657 0.70 700 0.81 747 0.93 793 1.08 837 1.22 873 1.35 905 1.47 935 1.58 963 1.70
3060 675 0.82 718 0.93 757 1.05 794 1.17 837 1.32 879 1.48 919 1.64 955 1.79 987 1.94 1014 2.07
3400 742 1.09 779 1.21 817 1.35 851 1.48 885 1.62 923 1.78 962 1.96 999 2.13 1033 2.31 1066 2.48
3740 810 1.44 842 1.56 878 1.70 911 1.85 941 1.99 972 2.14 1006 2.32 1041 2.51 1076 2.71 1109 2.90
4080 878 1.84 907 1.97 939 2.12 971 2.28 1000 2.44 1029 2.60 1056 2.76 1087 2.95 1120 3.16 1151 3.36
3 HP Over-Sized Motor & Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Drive 3 HP Over-Sized Motor & Drive
2720 989 1.82 1015 1.94 1038 2.05 1062 2.17 1085 2.29 1108 2.41 1129 2.53 1152 2.65 1172 2.77 1194 2.89
3060 1042 2.20 1067 2.34 1092 2.47 1115 2.60 1138 2.74 1159 2.87 1180 3.00 1200 3.13 1221 3.26 1241 3.40
3400 1093 2.64 1118 2.78 1144 2.94 1167 3.08 1190 3.23 1212 3.38 1233 3.53 1253 3.67 1273 3.82 1292 3.97
3740 1140 3.10 1169 3.28 1195 3.46 1219 3.63 1242 3.79 1264 3.96 1286 4.12 1307 4.28 1326 4.44 - -
4080 1182 3.57 1213 3.79 1241 4.00 1268 4.21 1292 4.40 - - --------
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.