29RT-PRC017-EN
Performance
Data
Table PD-16 - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Downflow Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4080 - - 697 0.46 745 0.53 790 0.60 830 0.66 869 0.73 906 0.80 941 0.87 976 0.94 1009 1.01
4590 717 0.55 760 0.62 804 0.69 847 0.77 887 0.85 922 0.92 958 0.99 991 1.07 1024 1.14 1055 1.22
5100 787 0.74 826 0.81 865 0.89 905 0.98 943 1.06 979 1.15 1012 1.23 1044 1.31 1075 1.39 1105 1.47
5610 858 0.97 894 1.05 929 1.13 965 1.22 1001 1.32 1036 1.41 1068 1.50 1099 1.59 1129 1.68 1157 1.77
6120 930 1.24 963 1.33 995 1.42 1028 1.51 1061 1.61 1093 1.71 1126 1.82 1157 1.92 1185 2.02 1212 2.11
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Drive 1.50 Nom kW Std Motor
& Hi Static Drive
4080 1042 1.09 1073 1.17 1104 1.24 1134 1.32 1163 1.40
4590 1086 1.30 1117 1.39 1146 1.47 1174 1.56 1203 1.65
5100 1134 1.56 1163 1.65 1191 1.74 1218 1.83 1245 1.92
5610 1185 1.86 1212 1.95 1238 2.04 1265 2.14 1292 2.24
6120 1239 2.21 1265 2.31 1290 2.40 1316 2.51 1340 2.61
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
2.24 Nom kW Over-Sized
Motor & Hi Static Drive
Table PD-16a - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Downflow Configuration - (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Low Static Drive 2 HP Standard Motor & Drive
2400 - - 697 0.62 745 0.71 790 0.80 830 0.89 869 0.98 906 1.07 941 1.16 976 1.26 1009 1.36
2700 717 0.74 760 0.83 804 0.93 847 1.03 887 1.13 922 1.23 958 1.33 991 1.43 1024 1.53 1055 1.64
3000 787 0.99 826 1.09 865 1.20 905 1.31 943 1.42 979 1.54 1012 1.64 1044 1.76 1075 1.87 1105 1.98
3300 858 1.30 894 1.41 929 1.52 965 1.64 1001 1.77 1036 1.89 1068 2.01 1099 2.13 1129 2.25 1157 2.37
3600 930 1.66 963 1.78 995 1.90 1028 2.03 1061 2.16 1093 2.30 1126 2.43 1157 2.57 1185 2.70 1212 2.83
3 HP Over-Sized Motor & Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor &
2 HP Standard Motor & Drive Hi Static Drive
2400 1042 1.46 1073 1.56 1104 1.67 1134 1.77 1163 1.87
2700 1086 1.75 1117 1.86 1146 1.97 1174 2.09 1203 2.21
3000 1134 2.09 1163 2.21 1191 2.33 1218 2.45 1245 2.58
3300 1185 2.49 1212 2.61 1238 2.74 1265 2.87 1292 3.01
3600 1239 2.96 1265 3.09 1290 3.22 1316 3.36 1340 3.49
3 HP Over-Sized Mtr & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.