Trane YSC060-120 Air Conditioner User Manual


 
35RT-PRC017-EN
Performance
Data
Table PD-22 - Belt Drive Evaporator Fan Performance - YSC120AD*L - Low Heat - Downflow Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Low Static Drive 2.24 Nom kW Standard
Motor & Drive
5440 - - - - 691 0.66 727 0.75 763 0.85 798 0.95 832 1.06 863 1.16 895 1.27 924 1.39
6120 - - 717 0.77 751 0.86 784 0.95 816 1.06 848 1.17 879 1.29 910 1.41 940 1.53 968 1.64
6800 746 0.90 780 1.00 813 1.11 843 1.21 873 1.31 902 1.43 931 1.56 959 1.69 986 1.82 1014 1.94
7480 814 1.17 845 1.29 876 1.41 905 1.52 932 1.63 959 1.74 985 1.87 1012 2.01 1037 2.14 1063 2.29
8160 883 1.50 911 1.62 940 1.75 967 1.88 993 2.00 1018 2.12 1042 2.24 1067 2.38 1091 2.53 1115 2.68
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 Nom kW Standard Motor & Drive
5440 952 1.50 979 1.63 1004 1.75 1029 1.87 1053 2.00 1078 2.13 1101 2.27 1124 2.41 1146 2.54 1169 3.59
6120 996 1.77 1023 1.89 1049 2.02 1073 2.15 1097 2.29 1120 2.43 1142 2.56 1164 2.71 1186 2.85 1207 4.02
6800 1041 2.08 1067 2.21 1092 2.34 1117 2.48 1141 2.62 1164 2.76 1186 2.91 1208 3.06 1228 3.20 - -
7480 1088 2.43 1113 2.57 1137 2.72 1162 2.87 1185 3.01 1207 3.16 1229 3.30 - - - - - -
8160 1139 2.83 1161 2.99 1185 3.15 1208 3.30 - - - - --------
2.24 Nom kW Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-22a - Belt Drive Evaporator Fan Performance - YSC120AD*L - Low Heat - Downflow Configuration - (IP)
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Low Static Drive 3 HP Std Motor & Drive
3200 - - - - 691 0.88 727 1.00 763 1.14 798 1.28 832 1.42 863 1.56 895 1.71 924 1.86
3600 - - 717 1.03 751 1.15 784 1.28 816 1.42 848 1.57 879 1.73 910 1.89 940 2.05 968 2.20
4000 746 1.21 780 1.35 813 1.49 843 1.62 873 1.76 902 1.92 931 2.09 959 2.26 986 2.43 1014 2.61
4400 814 1.57 845 1.73 876 1.88 905 2.03 932 2.18 959 2.34 985 2.51 1012 2.69 1037 2.88 1063 3.07
4800 883 2.02 911 2.18 940 2.35 967 2.52 993 2.68 1018 2.84 1042 3.01 1067 3.20 1091 3.39 1115 3.59
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive
3200 952 2.01 979 2.18 1004 2.34 1029 2.51 1053 2.68 1078 2.86 1101 3.04 1124 3.23 1146 3.41 1169 3.59
3600 996 2.37 1023 2.53 1049 2.71 1073 2.88 1097 3.07 1120 3.25 1142 3.43 1164 3.63 1186 3.83 1207 4.02
4000 1041 2.79 1067 2.96 1092 3.14 1117 3.33 1141 3.51 1164 3.7 1186 3.90 1208 4.10 1228 4.30 - -
4400 1088 3.26 1113 3.45 1137 3.64 1162 3.84 1185 4.04 1207 4.23 1229 4.43 - - - - - -
4800 1139 3.80 1161 4.00 1185 4.22 1208 4.43 - - - - --------
3 HP Standard Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.