Trane YSC060-120 Air Conditioner User Manual


 
RT-PRC017-EN28
Performance
Data
Table PD-15 - Belt Drive Evaporator Fan Performance - YSC090AD*L - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4080 - - 694 0.44 745 0.50 793 0.58 835 0.64 874 0.70 911 0.77 948 0.85 982 0.92 1017 1.00
4590 725 0.54 760 0.60 801 0.66 847 0.73 889 0.82 927 0.89 963 0.96 997 1.03 1030 1.11 1061 1.19
5100 798 0.73 830 0.79 862 0.86 902 0.93 943 1.01 981 1.10 1017 1.19 1050 1.27 1081 1.34 1111 1.42
5610 872 0.96 901 1.03 929 1.10 961 1.17 998 1.25 1036 1.34 1071 1.44 1104 1.54 1135 1.63 1164 1.71
6120 946 1.23 973 1.31 1000 1.38 1025 1.45 1057 1.54 1091 1.62 1125 1.72 1158 1.83 1189 1.95 1219 2.05
2.24 Nom kW Over-Sized
Motor & Hi Static Drive
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Drive 1.50 Nom kW Std Mtr
& Hi Static Drive
4080 1053 1.08 1087 1.15 1121 1.23 1153 1.31 1185 1.39
4590 1093 1.28 1124 1.37 1156 1.45 1187 1.54 1218 1.63
5100 1141 1.51 1170 1.60 1198 1.70 1227 1.80 1255 1.89
5610 1192 1.79 1220 1.88 1247 1.98 1272 2.07 1299 2.18
6120 1246 2.14 1272 2.23 1298 2.32 1323 2.41 1348 2.52
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
1.50 Nom kW Std Mtr
& Hi Static Drive
Table PD-15a - Belt Drive Evaporator Fan Performance - YSC090AD*L - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Low Static Drive 2 HP Standard Motor & Drive
2400 - - 694 0.59 745 0.67 793 0.77 835 0.86 874 0.94 911 1.03 948 1.13 982 1.23 1017 1.34
2700 725 0.73 760 0.80 801 0.88 847 0.98 889 1.09 927 1.19 963 1.28 997 1.38 1030 1.48 1061 1.60
3000 798 0.98 830 1.06 862 1.15 902 1.24 943 1.35 981 1.48 1017 1.60 1050 1.70 1081 1.80 1111 1.90
3300 872 1.28 901 1.38 929 1.47 961 1.56 998 1.67 1036 1.80 1071 1.93 1104 2.07 1135 2.19 1164 2.30
3600 946 1.65 973 1.75 1000 1.85 1025 1.95 1057 2.06 1091 2.17 1125 2.31 1158 2.46 1189 2.61 1219 2.75
3 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Drive 2 HP Standard Motor
& Hi Static Drive
2400 1053 1.44 1087 1.55 1121 1.65 1153 1.76 1185 1.86
2700 1093 1.71 1124 1.83 1156 1.95 1187 2.06 1218 2.18
3000 1141 2.02 1170 2.15 1198 2.28 1227 2.41 1255 2.54
3300 1192 2.41 1220 2.52 1247 2.65 1272 2.78 1299 2.92
3600 1246 2.87 1272 2.99 1298 3.11 1323 3.24 1348 3.37
3 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
2 HP Std Mtr & Hi Static Drive