Trane YSC060-120 Air Conditioner User Manual


 
RT-PRC017-EN20
Performance
Data
Table PD-7 - Belt Drive Evaporator Fan Performance - YSC060AD*L - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Std Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
2720 788 0.33 850 0.38 911 0.44 964 0.49 1011 0.55 1055 0.61 1097 0.66 1137 0.72 1176 0.78 1213 0.84
3060 871 0.45 927 0.51 983 0.57 1035 0.64 1082 0.70 1124 0.76 1164 0.83 1201 0.89 1239 0.95 1275 1.02
3400 956 0.60 1006 0.67 1057 0.74 1106 0.81 1153 0.88 1195 0.95 1233 1.02 1270 1.09 1305 1.16 1339 1.23
3740 1042 0.78 1088 0.85 1133 0.93 1179 1.01 1224 1.09 1266 1.16 1305 1.24 1340 1.32 - - - -
4080 1129 1.00 1171 1.08 1213 1.16 1255 1.25 1296 1.33 - - --------
External Static Pressure (Pascals)
275 300 325 350 375
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Drive
2720 1248 0.91 1282 0.97 1314 1.04 1344 1.11 1374 1.18
3060 1310 1.09 1344 1.16 - - - - - -
3400 1373 1.30 - - - - - - - -
3740 - - - - - - - - - -
4080 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-7a - Belt Drive Evaporator Fan Performance - YSC060AD*L - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive
1600 788 0.44 850 0.51 911 0.59 964 0.66 1011 0.74 1055 0.81 1097 0.89 1137 0.97 1176 1.05 1213 1.13
1800 871 0.60 927 0.68 983 0.77 1035 0.85 1082 0.94 1124 1.02 1164 1.11 1201 1.19 1239 1.28 1275 1.37
2000 956 0.80 1006 0.89 1057 0.99 1106 1.08 1153 1.18 1195 1.27 1233 1.36 1270 1.46 1305 1.55 1339 1.65
2200 1042 1.05 1088 1.15 1133 1.25 1179 1.35 1224 1.46 1266 1.56 1305 1.66 1340 1.77 1375 - - -
2400 1129 1.34 1171 1.45 1213 1.56 1255 1.67 1296 1.78 - - --------
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Drive
1600 1248 1.21 1282 1.30 1314 1.39 1344 1.48 1374 1.58
1800 1310 1.46 1344 1.55 - - - - - -
2000 1373 1.75 - - - - - - - -
2200 - - - - - - - - - -
2400 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.