Trane YSC060-120 Air Conditioner User Manual


 
RT-PRC017-EN34
Performance
Data
Table PD-21 - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Low Static Drive 1.50 Nom kW Standard Motor & Drive
4620 651 0.51 694 0.59 740 0.68 787 0.79 831 0.89 869 0.99 901 1.08 931 1.17 959 1.26 986 1.35
5200 722 0.70 761 0.79 798 0.88 841 1.00 883 1.11 923 1.23 958 1.35 989 1.45 1017 1.55 1045 1.65
5780 793 0.94 830 1.04 863 1.14 898 1.25 937 1.37 975 1.51 1011 1.64 1045 1.77 1075 1.89 1103 2.01
6350 865 1.23 899 1.34 930 1.45 961 1.56 994 1.68 1028 1.82 1063 1.96 1097 2.11 1129 2.26 1159 2.40
6930 937 1.57 970 1.70 999 1.81 1027 1.93 1055 2.05 1085 2.19 1118 2.34 1150 2.50 1181 2.66 1211 2.82
2.24 Nom kW Over-Sized Motor & High Static Drive
External Static Pressure (Pascals)
275 300 325 350 375 400 425 450 475 500
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr & Drive
4620 1011 1.43 1036 1.52 1059 1.61 1082 1.69 1104 1.78 1127 1.87 1149 1.96 1170 2.05 1191 2.14 1212 2.24
5200 1070 1.75 1094 1.85 1117 1.95 1139 2.05 1161 2.15 1182 2.24 1203 2.35 1222 2.44 1243 2.54 1262 2.64
5780 1128 2.12 1152 2.23 1176 2.34 1198 2.45 1219 2.56 1241 2.67 1261 2.78 1280 2.88 1299 2.99 1319 3.11
6350 1186 2.53 1210 2.65 1233 2.78 1256 2.90 1278 3.03 1298 3.15 1319 3.27 - - - - - -
6930 1239 2.97 1267 3.13 1291 3.27 - - - - - - --------
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-21a - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Low Static Drive 2 HP Standard Motor & Drive
2720 651 0.69 694 0.79 740 0.92 787 1.06 831 1.20 869 1.33 901 1.45 931 1.57 959 1.69 986 1.81
3060 722 0.94 761 1.06 798 1.18 841 1.34 883 1.49 923 1.65 958 1.81 989 1.95 1017 2.08 1045 2.22
3400 793 1.26 830 1.40 863 1.53 898 1.67 937 1.84 975 2.02 1011 2.20 1045 2.37 1075 2.54 1103 2.69
3740 865 1.65 899 1.80 930 1.94 961 2.09 994 2.26 1028 2.44 1063 2.63 1097 2.83 1129 3.03 1159 3.22
4080 937 2.11 970 2.27 999 2.43 1027 2.59 1055 2.75 1085 2.94 1118 3.14 1150 3.35 1181 3.57 1211 3.78
3 HP Over-Sized Motor & Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Drive 3 HP Over-Sized Motor & Drive
2720 1011 1.92 1036 2.04 1059 2.15 1082 2.27 1104 2.39 1127 2.51 1149 2.64 1170 2.75 1191 2.88 1212 3.00
3060 1070 2.35 1094 2.48 1117 2.61 1139 2.75 1161 2.88 1182 3.01 1203 3.15 1222 3.27 1243 3.41 1262 3.54
3400 1128 2.84 1152 2.99 1176 3.14 1198 3.29 1219 3.43 1241 3.58 1261 3.73 1280 3.87 1299 4.02 1319 4.17
3740 1186 3.40 1210 3.56 1233 3.73 1256 3.90 1278 4.06 1298 4.22 1319 4.39 - - - - - -
4080 1239 3.99 1267 4.20 1291 4.39 - - - - - - --------
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.