Trane YSC060-120 Air Conditioner User Manual


 
19RT-PRC017-EN
Performance
Data
Table PD-6 - Belt Drive Evaporator Fan Performance - YSC060AD*L - Low Heat - Downflow Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Low Static Drive 1.12 Nom kW Std Mtr & Drive
2720 716 0.28 768 0.32 816 0.36 863 0.39 909 0.44 953 0.50 993 0.55 1031 0.60 1067 0.65 1101 0.70
3060 791 0.38 840 0.43 884 0.47 927 0.51 969 0.56 1010 0.61 1049 0.67 1087 0.73 1122 0.79 1156 0.85
3400 867 0.51 914 0.56 955 0.61 994 0.66 1033 0.71 1070 0.76 1107 0.82 1143 0.88 1178 0.95 1212 1.02
3740 944 0.66 989 0.73 1027 0.78 1063 0.84 1099 0.89 1134 0.94 1168 0.99 1202 1.05 1235 1.12 1267 1.19
4080 1022 0.85 1064 0.92 1101 0.98 1135 1.04 1168 1.10 1200 1.16 1233 1.22 - - - - - -
Table PD-6a - Belt Drive Evaporator Fan Performance - YSC060AD*L - Low Heat - Downflow Configuration - (IP)
External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Std Motor & Drive
1600 716 0.37 768 0.43 816 0.48 863 0.53 909 0.60 953 0.67 993 0.74 1031 0.81 1067 0.87 1101 0.94
1800 791 0.51 840 0.57 884 0.63 927 0.69 969 0.75 1010 0.82 1049 0.90 1087 0.99 1122 1.06 1156 1.14
2000 867 0.68 914 0.76 955 0.82 994 0.89 1033 0.95 1070 1.02 1107 1.10 1143 1.18 1178 1.27 1212 1.36
2200 944 0.89 989 0.97 1027 1.05 1063 1.12 1099 1.19 1134 1.26 1168 1.33 1202 1.41 1235 1.51 1267 1.60
2400 1022 1.14 1064 1.23 1101 1.32 1135 1.40 1168 1.48 1200 1.55 1233 1.63 - - - - - -
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
External Static Pressure (Pascals)
275 300 325 350 375
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Drive
2720 1135 0.75 1166 0.80 1198 0.85 1228 0.91 1258 0.96
3060 1188 0.90 1218 0.96 1249 1.01 1279 1.07 1307 1.13
3400 1244 1.08 1273 1.14 1303 1.20 1332 1.27 - -
3740 1300 1.27 - - - - - - - -
4080 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Drive
1600 1135 1.01 1166 1.07 1198 1.14 1228 1.22 1258 1.29
1800 1188 1.21 1218 1.28 1249 1.36 1279 1.44 1307 1.51
2000 1244 1.45 1273 1.53 1303 1.61 1332 1.70 - -
2200 1300 1.70 - - - - - - - -
2400 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451