Trane YSC060-120 Air Conditioner User Manual


 
21RT-PRC017-EN
Performance
Data
Table PD-8 - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Downflow Configuration - (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Low Static Drive 1.12 Nom kW Std Mtr & Drive
2720 734 0.29 784 0.33 833 0.37 879 0.41 924 0.46 967 0.52 1007 0.57 1043 0.62 1078 0.67 1113 0.72
3060 813 0.40 859 0.45 903 0.49 945 0.53 987 0.58 1027 0.64 1066 0.70 1103 0.76 1137 0.82 1169 0.87
3400 894 0.54 936 0.59 976 0.64 1014 0.69 1052 0.73 1089 0.79 1126 0.85 1162 0.92 1196 0.98 1229 1.05
3740 974 0.70 1014 0.76 1051 0.82 1087 0.87 1122 0.92 1156 0.98 1190 1.03 1224 1.10 1257 1.17 1288 1.24
4080 1055 0.90 1093 0.97 1127 1.03 1160 1.09 1193 1.15 1225 1.20 1256 1.26 1288 1.32 - - - -
External Static Pressure (Pascals)
275 300 325 350 375
m3/h RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Drive
2720 1145 0.77 1177 0.82 1208 0.87 1238 0.93 1268 0.98
3060 1202 0.93 1232 0.98 1262 1.04 1290 1.09 1319 1.15
3400 1260 1.11 1289 1.17 1319 1.24 1347 1.30 - -
3740 1320 1.32 - - - - - - - -
4080 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-8a - Belt Drive Evaporator Fan Performance - YSC060AD*H - High Heat - Downflow Configuration - (IP)
External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Std Motor & Drive
1600 734 0.39 784 0.44 833 0.49 879 0.55 924 0.62 967 0.69 1007 0.76 1043 0.83 1078 0.89 1113 0.96
1800 813 0.54 859 0.60 903 0.66 945 0.72 987 0.78 1027 0.86 1066 0.94 1103 1.02 1137 1.09 1169 1.17
2000 894 0.72 936 0.79 976 0.86 1014 0.92 1052 0.98 1089 1.06 1126 1.14 1162 1.23 1196 1.32 1229 1.41
2200 974 0.94 1014 1.02 1051 1.10 1087 1.17 1122 1.24 1156 1.31 1190 1.38 1224 1.47 1257 1.57 1288 1.67
2400 1055 1.21 1093 1.30 1127 1.38 1160 1.46 1193 1.54 1225 1.61 1256 1.69 1288 1.77 - - - -
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Drive
1600 1145 1.03 1177 1.10 1208 1.17 1238 1.24 1268 1.31
1800 1202 1.24 1232 1.32 1262 1.39 1290 1.47 1319 1.55
2000 1260 1.49 1289 1.57 1319 1.66 1347 1.74 - -
2200 1320 1.77 - - - - - - - -
2400 - - - - - - - - - -
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.