Trane YSC060-120 Air Conditioner User Manual


 
RT-PRC017-EN30
Performance
Data
Table PD-17a - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Motor & Low Static Drive 2 HP Standard Motor & Drive
2400 713 0.62 764 0.71 811 0.81 851 0.89 889 0.97 926 1.07 962 1.17 997 1.28 1031 1.38 1067 1.48
2700 790 0.86 837 0.96 880 1.07 919 1.17 955 1.26 989 1.36 1022 1.46 1054 1.57 1086 1.69 1117 1.80
3000 869 1.16 910 1.26 950 1.38 989 1.50 1023 1.62 1056 1.72 1086 1.82 1116 1.92 1146 2.04 1175 2.17
3300 949 1.53 985 1.63 1023 1.75 1058 1.88 1092 2.02 1124 2.15 1154 2.26 1182 2.37 1210 2.48 1237 2.60
3600 1029 1.97 1061 2.07 1096 2.19 1130 2.33 1162 2.48 1193 2.63 1222 2.77 1250 2.89 1276 3.01 1302 3.13
3 HP Over-Sized Motor & Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Std Mtr & Drive 2 HP Standard Motor
& Hi Static Drive
2400 1101 1.59 1134 1.69 1166 1.80 1197 1.90 1229 2.02
2700 1148 1.92 1180 2.04 1210 2.15 1241 2.27 1269 2.39
3000 1204 2.30 1232 2.43 1260 2.56 1287 2.69 1316 2.82
3300 1264 2.74 1290 2.87 1316 3.02 1342 3.16 1367 3.30
3600 1327 3.26 1352 3.39 1376 3.54 1401 3.69 1425 3.85
3 HP Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
2 HP Std Mtr & Hi Static Drive
Table PD-17 - Belt Drive Evaporator Fan Performance - YSC090AD*H - High Heat - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Standard Motor 1.50 Nom kW Standard Motor & Drive
& Low Static Drive
4080 713 0.46 764 0.53 811 0.61 851 0.67 889 0.73 926 0.80 962 0.88 997 0.95 1031 1.03 1067 1.11
4590 790 0.64 837 0.71 880 0.80 919 0.88 955 0.94 989 1.01 1022 1.09 1054 1.17 1086 1.26 1117 1.35
5100 869 0.87 910 0.94 950 1.03 989 1.12 1023 1.21 1056 1.28 1086 1.36 1116 1.43 1146 1.52 1175 1.62
5610 949 1.14 985 1.22 1023 1.30 1058 1.40 1092 1.51 1124 1.60 1154 1.68 1182 1.77 1210 1.85 1237 1.94
6120 1029 1.47 1061 1.55 1096 1.64 1130 1.74 1162 1.85 1193 1.96 1222 2.06 1250 2.16 1276 2.25 1302 2.34
2.24 Nom kW Over-Sized
Motor & Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
1.50 Nom kW Std Mtr
& Hi Static Drive
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.50 Nom kW Std Mtr 1.50 Nom kW Standard Motor
& Drive & Hi Static Drive
4080 1101 1.19 1134 1.26 1166 1.34 1197 1.42 1229 1.50
4590 1148 1.43 1180 1.52 1210 1.60 1241 1.69 1269 1.78
5100 1204 1.72 1232 1.81 1260 1.91 1287 2.00 1316 2.10
5610 1264 2.04 1290 2.14 1316 2.25 1342 2.36 1367 2.46
6120 1327 2.43 1352 2.53 1376 2.64 1401 2.75 1425 2.87
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139