RT-PRC017-EN26
Performance
Data
Table PD-13 - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25 50 75 100 125 150 175 200 225 250
m
3
/h RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor & Low Static Drive 1.12 Nom kW Standard Motor & Drive
3260 579 0.24 639 0.30 690 0.35 736 0.40 780 0.46 824 0.52 866 0.59 907 0.65 947 0.71 986 0.78
3670 636 0.33 692 0.39 741 0.46 784 0.51 826 0.57 865 0.64 903 0.71 943 0.78 979 0.84 1017 0.91
4080 696 0.45 746 0.51 794 0.58 836 0.64 874 0.70 911 0.77 947 0.84 982 0.92 1017 1.00 1051 1.07
4490 757 0.58 802 0.64 847 0.72 888 0.80 924 0.86 959 0.93 993 1.00 1026 1.08 1058 1.17 1089 1.25
4890 818 0.74 858 0.81 900 0.88 940 0.97 977 1.05 1010 1.13 1042 1.20 1073 1.27 1104 1.36 1133 1.45
1.12 Nom kW Standard Motor & Drive
1.50 Nom kW Over-Sized Motor
& High Static Drive
External Static Pressure (Pascals)
275 300 325 350 375
CFM RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 Nom kW Standard Motor
& Hi Static Drive
3260 1023 0.84 1059 0.92 1093 0.98 1126 1.06 1156 1.12
3670 1053 0.98 1087 1.06 1121 1.13 1153 1.21 1185 1.29
4080 1085 1.15 1119 1.23 1151 1.30 1182 1.38 1214 1.47
4490 1122 1.34 1153 1.42 1184 1.50 1215 1.59 - -
4890 1163 1.54 1192 1.64 1221 1.72 - - - -
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
1.12 Nom kW Std Mtr
& Hi Static Drive
←←
←←
←
Table PD-13a - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Low Static Drive 1-1/2 HP Standard Motor & Drive
1920 579 0.33 639 0.40 690 0.47 736 0.54 780 0.62 824 0.70 866 0.79 907 0.87 947 0.95 986 1.04
2160 636 0.45 692 0.53 741 0.61 784 0.68 826 0.76 865 0.85 903 0.95 943 1.04 979 1.13 1017 1.23
2400 696 0.60 746 0.68 794 0.78 836 0.86 874 0.94 911 1.03 947 1.13 982 1.23 1017 1.34 1051 1.44
2640 757 0.78 802 0.86 847 0.96 888 1.07 924 1.16 959 1.25 993 1.35 1026 1.45 1058 1.56 1089 1.68
2880 818 1.00 858 1.08 900 1.18 940 1.30 977 1.41 1010 1.51 1042 1.61 1073 1.71 1104 1.82 1133 1.94
1-1/2 HP Standard Motor & Drive 2 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1-1/2 HP Standard Motor & Hi Static Drive
1920 1023 1.13 1059 1.23 1093 1.32 1126 1.42 1156 1.51
2160 1053 1.32 1087 1.42 1121 1.52 1153 1.62 1185 1.72
2400 1085 1.54 1119 1.65 1151 1.75 1182 1.85 1214 1.96
2640 1122 1.79 1153 1.90 1184 2.01 1215 2.13 - -
2880 1163 2.07 1192 2.19 1221 2.31 - - - -
2 HP Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
1-1/2 HP Std Motor
& Hi Static Drive
←←
←←
←