Summary of BACnet Objects
(X13511541010 and -2010) Rooftop and Heat Pump Models
Default Device ID is set to: 7600MAC where MAC is the current MAC address of the device.
The device ID and the Device Name change if you change the device’s MAC address. For
example, when aheat pump communicatingthermostat with aMAC address of63 is connected
to a network, its default Device Name will be TStat_HeatPump_Trane_63 and its default Device
ID will be 760063.
Fan Coil Objects
Table 2. Objects table for fan coils (X13511543010)
Object Name Type and Instance Object Property
Room Temperature AV 7 Present_Value (R,W)
Room Temp Override BV 8 Present_Value (R,W)
Outdoor Temperature AV 9 Present_Value (R,W)
Supply Temperature AI 12 Present_Value (R)
AUX Command BV 14 Present_Value (R,W)
Sequence of Operation MV 15 Present_Value (R,W)
System Mode MV 16 Present_Value (R,W)
Fan Mode MV 17 Present_Value (R,W)
Occupancy Command MV 18 Present_Value (R,W)
Keypad Lockout MV 19 Present_Value (R,W)
Control Output GRP 20 Present_Value (R)
PI Heating Demand AV 21 Present_Value (R)
PI Cooling Demand AV 22 Present_Value (R)
Controller Status GRP 24 Present_Value (R)
AUX Status BI 25 Present_Value (R)
Heating Valve Status MV 26 Present_Value (R)
Cooling Valve Status MV 27 Present_Value (R)
Fan Status MV 28 Present_Value (R)
BI 1 Status BI 29 Present_Value (R)
BI 2 Status BI 30 Present_Value (R)
UI 3 Status BI 31 Present_Value (R)
Local Motion BI 32 Present_Value (R)
Effective Occupancy MV 33 Present_Value (R)
Controller Alarms GRP 34 Present_Value (R)
Window Alarm BI 35 Present_Value (R)
Filter Alarm BI 36 Present_Value (R)
Service Alarm BI 37 Present_Value (R)
Temperature Setpoints GRP 38 Present_Value (R)
Occupied Heat Setpoint AV 39 Present_Value (R,W)
Occupied Cool Setpoint AV 40 Present_Value (R,W)
Stand-by Heat Setpoint AV 41 Present_Value (R,W)
Stand-by Cool Setpoint AV 42 Present_Value (R,W)