BACnet Object Properties
Humidifier Output AV 101 0% 100% N/A
Table 15. List of property enumeration sets for BI and BV objects
Object Name
Object Type
and Instance Inactive_Text Active_Text Default Value
Room Temp Override BV 8 Normal Override Normal
Outdoor Temp Override BV 10 Normal Override Normal
AUX BI 24 Off On Off
G Fan BI 25 Off On Off
Y1 Cool BI 26 Off On Off
Y2 Cool BI 27 Off On Off
W1 Heat BI 28 Off On Off
W2 Heat BI 29 Off On Off
Reversing Valve BI 30 Off On Off
DI 1 Status BI 31 Not Activated Activated Not Activated
DI 2 Status BI 32 Not Activated Activated Not Activated
Local Motion BI 33 No Motion Motion No Motion
Frost Alarm BI 36 Off On Off
Clock Alarm BI 37 Off On Off
Filter Alarm BI 38 Off On Off
Service Alarm BI 39 Off On Off
Fan Lock Alarm BI 40 Off On Off
Temperature Scale BV 47 °C °F °F
Frost Protection BV 55 Off On Off
Aux Contact BV 56 N.O. N.C. N.O.
Menu Scroll BV 57 No Scroll Scroll Active Scroll Active
Fan Control BV 62 Off On On
Fan Purge Delay BV 64 Off On Off
Progressive Recovery BV 70 Off Active Off
Mechanical Cooling Enabled BV 79 Off On Off
Comfort Mode BV 84 Comfort Economy Comfort
Reversing Valve
Configuration
BV 85
Normally Cool
Energized in Heating
Normally Heat
Energized in
Cooling
Normally Heat
Energized in
Cooling
Compressor Interlock BV 86 Off On Off
RH Display BV 88 Disabled Enabled Disabled
Dehumidification Lockout
Functions
BV 92 Disabled Enabled Enabled
Dehumidification Output
Status
BI 93 Off On N/A
Table 14. List of property value range restrictions for AI and AV objects (continued)
Object Name
Object Type
and Instance
Under Range
Value Over Range Value Default Value