Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
BAS-SVP10A-EN 15
BACnet Object Properties
* This object will be linked to the value of the ‘UI 3 Configuration’ object. When the ‘UI 3 Configuration’ object value is 0, 3
or 4, the value will be set to ‘Deactivated.’
Table 8. List of property enumeration sets for MV objects
Table Notes:
1 Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required enumeration
is not present, set MV15 to desired value and rediscover MV16 object. Available enumeration will now reflect required
configuration.
2 Default value of MV16 depends on MV15 value upon device discovery. (See Table 9.)
Filter Alarm BI 36 Off On Off
Service Alarm BI 37 Off On Off
Menu Scroll BV 49 No Scroll Scroll Active Scroll Active
Auto Mode Enable BV 50 Disabled Enabled Enabled
Temperature Scale BV 51 °C °F °F
Setpoint Type BV 60 Permanent Temporary Permanent
Setpoint Function BV 61 Dual Setpoints Attached Setpoints Dual Setpoints
Reheat Time Base BV 64 15 minutes 10 seconds 15 minutes
Auto Fan BV 66 Auto Speed
Auto Speed / Auto
Demand
Auto Speed
RH Display BV 70 Disabled Enabled Disabled
Control Type BV 75 On/Off Floating On/Off
Direct/ Reverse Acting BV 78 Direct Acting Reverse Acting Direst Acting
Table 7. List of property enumeration sets for BV objects and BI objects (continued)
Object Name
Object Type and
instance Inactive_Text Active_Text Default value
Object Name Object ID BACnet Index Text Default value
Sequence of
Operation
1 Cooling Only
Heating Only
2 Heating Only
MV 15 3 Cooling & Reheat
4 Heating & Reheat
5 Cool/Heat4P
6 Cool/Heat4P&Reht
System Mode
Table Note 1
1 Off
Table Note 2
MV 16 2 Auto
3 Cool
4 Heat
Fan Mode
Table Note 3
MV 17 1, 2, 3 or 4 Table Note 4 Table Note 5
Occupancy Command
MV 18 1 Local Occupancy
Depends on network
command
2 Occupied
3 Unoccupied
Keypad Lockout MV 19
1 Level 0
Level 0
2 Level 1
3 Level 2
4 Level 3
5 Level 4
6 Level 5