Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
BAS-SVP10A-EN 17
BACnet Object Properties
meration will now reflect required configuration.
9 Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52) upon
device discovery. (See Table 12.)
BV75 Value MV52 Index MV27 Object Name
Function MV26
State Text Index Default Value
On/Off
1 (2 pipe) Heat/Cool Valve Status 1 Closed – 2 Open Closed
2 (4 pipe) Cooling Valve Status 1 Closed – 2 Open Closed
Floating
1 (2 pipe) Heat/Cool Valve Status
1 Stopped - 2 Opening -
3 Closing
Stopped
2 (4 pipe) Cooling Valve Status
1 Stopped - 2 Opening -
3 Closing
Stopped
Table 12. Various object indexes and values for Note 9
Table 13. Additional MV Values
Object Name Object ID BACnet Index Text Default Value
BI1 Configuration MV 46
1 None
None
2 Rem NSB
3 Motion NO
4 Motion NC
5 Window
BI2 Configuration MV 47
1 None
None
2 Door Dry
3 Override
4 Filter
5 Service
UI3 Configuration MV 48
1 None
None
2 COC/NH
3 COC/NC
4 COS
5 SS
Pipe Number MV 52
1 2 Pipe
4 Pipes
2 4 Pipe
Out#1 Cfg MV 53
1 2
4
2 4
AUX Configuration MV 54
1 Not used
Not Used
2 NO with Occ
3 NC with Occ
4 NO with Occ & Fan
5 NC with Occ & Fan
6 Network controlled
Fan Mode Sequence MV 58
1 Low-Med-High
On-Auto
2 Low-High
3 Low-Med-High-Auto
4 Low-High-Auto
5 On-Auto