Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
BAS-SVP10A-EN 19
BACnet Object Properties
Rooftop and Heat Pump Object Properties
On-Off Control
CPH MV 77
1 3 CPH
4 CPH
2 4 CPH
3 5 CPH
4 6 CPH
5 7 CPH
6 8 CPH
Table 13. Additional MV Values (continued)
Object Name Object ID BACnet Index Text Default Value
Table 14. List of property value range restrictions for AI and AV objects
Object Name
Object Type
and Instance
Under Range
Value Over Range Value Default Value
Room Temperature AV 7 -40°F (-40°C) 122°F (50°C) N/A
Outdoor Temperature AV 9 -40°F (-40°C) 122°F (50°C) N/A
Room Humidity AV 11 0% 100% N/A
Supply Temp AI 16 -40°F (-40°C) 122°F (50°C) N/A
Supply RH AV 17 0% 100% N/A
PI Heating Demand AV 20 0% 100% N/A
PI Cooling Demand AV 21 0% 100% N/A
Economizer Output AV 22 0% 100% N/A
Occupied Heat Setpoint AV 42 40°F (4.5°C) 90°F (32°C) 72°F (22°C)
Occupied Cool Setpoint AV 43 54°F (12°C) 100°F (37.5°C) 75°F (24°C)
Unoccupied Heat Setpoint AV 44 40°F (4.5°C) 90°F (32°C) 62°F (16.5°C)
Unoccupied Cool Setpoint AV 45 54°F (12°C) 100°F (37.5) 80°F (26.5°C)
Heating Setpoint Limit AV 48 40°F (4.5°C) 90°F (32°C) 90°F (32°C)
Cooling Setpoint Limit AV 49 54°F (12°C) 100°F (37.5) 54°F (12°C)
Heating Lockout
Temperature
AV 50 -15°F (-26°C) 120°F (49°C) 120°F (49°C)
Cooling Lockout Temperature AV 51 -40°F (-40°C) 95°F (35°C) -40°F (-40°C)
Deadband AV 52 2°F (1°C) 4°F (2°C) 2°F (1°C)
Password Value AV 59 0 1000 0
Power-up Delay AV 60 10 sec 120 sec 10 sec
Unoccupied Time AV 68 0.5 hrs 24.0. hrs 0.5 hrs
Economizer Changeover
Setpoint
AV 77 14°F (-10°C) 70°F (21°C) 55°F (13°C)
Economizer Minimum
Position
AV 78 0% 100% 0%
Mixed Air Setpoint AV 80 50°F (10°C) 90°F (32°C) 55°F (13°C)
High Balance Point AV 82 34°F (1°C) 90°F (32°C) 90°F (32°C)
Low Balance Point AV 83 -40°F (-40°C) 30°F (-1°C) -12°F (-24°C)
Dehumidification RH
Setpoint
AV 89 15% 95% 70%
Dehumidification Hysterisys AV 90 2% 20% 5%
Dehumidification Low OA
Lockout
AV 91 -40°F (-40°C) 122°F (50°C) 32°F (0°C)
Humidification RH Setpoint AV 95 10% 90% 50%
Eff (Effective) Reset
Humidification RH Spt
(Setpoint)
AV 96 0% 100% N/A
Humidification High Limit Spt
(Setpoint)
AV 97 50% 90% 85%
Low RH Setpoint AV 98 10% 90% 20%
Low Temp Reset RH Setpoint AV 99 -40°F (-40°C) 15°F (-9.5°C) -20°F (-29°C)
High Temp Reset RH Setpoint AV 100 20°F (-6.5°C) 55°F (13°C) 32°F (0.0°C)