Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
BAS-SVP10A-EN 21
BACnet Object Properties
Table 16. List of property enumeration sets for MV objects
Object Name
Object Type and
instance BACnet Index Text Default Value
Occupancy Command MV12
1 Local Occupancy
Local Occupancy 2 Occupied
3 Unoccupied
System Mode HPU MV13
1 Off
Auto
2 Auto
3 Cool
4 Heat
5 Emergency
System Mode RTU MV14
1 Off
Auto
2 Auto
3 Cool
4 Heat
Fan Mode MV15
1 On
Smart2 Auto
3 Smart
Keypad Lockout MV18
1 Level 0
Level 02 Level 1
3 Level 2
Effective Occupancy MV 34
1 Occupied
Depends on local
occupancy
2 3 Unoccupied
3 Temporary Occupied
Heating CPH MV53
1 3 CPH
4 CPH
2 4 CPH
3 5 CPH
4 6 CPH
5 7 CPH
6 8 CPH
Cooling CPH MV54
1 3 CPH
4 CPH
2 4 CPH
Temporary Occupancy Time MV61
1 0 hour
3 hours
2 1 hour
3 2 hours
4 3 hours
5 4 hours
6 5 hours
7 6 hours
8 7 hours
9 8 hours
10 9 hours
11 10 hours
12 11 hours
13 12 hours
Anticycle MV63
1 0 minute
2 minutes
2 1 minute
3 2 minutes
4 3 minutes
5 4 minutes
6 5 minutes