Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
BAS-SVP10A-EN 45
Trane Communicating Thermostat Points List
Heat Output 2 Status W2 Heat BI 29
In Defrost Frost Protection BV 55
Keypad Lockout Keypad Lockout MV 18
Low Temperature Alarm Frost Alarm BI 36
Minimum Heating Cooling Setpoint
Differential
Deadband AV 52
Occupancy Input Local Motion BI 33
Occupancy Request Occupancy Command MV 12 Yes
Occupancy Status Effective Occupancy MV 34 Yes
Occupied Cooling Setpoint Occupied Cool Setpoint AV 43
Occupied Heating Setpoint Occupied Heat Setpoint AV 42
Outdoor Air Damper Position Economizer Output AV 22
Outdoor Air Temperature Outdoor Temperature AV 9
Space Temperature Active Room Temperature AV 7
Supply Fan Configuration Command Fan Control BV 62
Supply Fan Failure Fan Lockout Alarm BI 40
Timed Override Duration Setpoint Temporary Occupancy Time MV 61
Unoccupied Cooling Setpoint Unoccupied Cool Setpoint AV 45
Unoccupied Heating Setpoint Unoccupied Heat Setpoint AV 44
PI Heating Demand AV 20
PI Cooling Demand AV 21
Heating Setpoint Limit AV 48
Cooling Setpoint Limit AV 49
Heating Lockout
Temperature
AV 50
Cooling Lockout
Temperature
AV 51
Password Value AV 59
Power-up Delay AV 60
Unoccupied Time AV 68
AUX BI 24
DI 1 Status BI 31
DI 2 Status BI 32
Room Temp Override BV 8
Outdoor Temp Override BV 10
Aux Contact BV 56
Menu Scroll BV 57
Fan Purge Delay BV 64
Mechanical Cooling Enabled BV 79
Heating CPH MV 53
Cooling CPH MV 54
Anticycle MV 63
DI 1 Configuration MV 65
DI 2 Configuration MV 66
Proportional Band MV 67
Heating Stages MV 73
Cooling Stages MV 74
Table 46. Points Available in the TStat_RTU_Trane Template (continued)
Tracer SC Point Name
TStat Device Point
Name Point Type
Point
Instance
Data
Normaliza-
tion