Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
38 BAS-SVP10A-EN
Data Normalization
Tracer SC Point name: Supply Fan Staged Speed Status
BACnet point name, type, and instance: Fan Status (MV 28)
Tracer SC Point name: Fan Mode BAS
BACnet point name, type, and instance: Fan Mode (MV 17)
Table 28. Tracer SC writing to the fan coil (Supply Fan Staged Speed Status)
Tracer SC state and text Fan coil state and text
1 - Auto 4 - High
2 - Off 1 - Off
3 - Low 2 - Low
4 - Medium 3 - Medium
5 - High 4 - High
Table 29. Reading from fan coil to Tracer SC (Supply Fan Staged Speed Status)
Fan coil state and text Tracer SC state and text
1 - Off 2 - Off
2 - Low 3 - Low
3 - Medium 4 - Medium
4 - High 5 - High
Table 30. Tracer SC writing to the fan coil (Fan Mode BAS)
Tracer SC state and text Fan coil state and text
1 - On 2 - On
2 - Auto 1 - Auto
3 - Smart 1 - Auto
Table 31. Reading from fan coil to tracer SC (Fan Mode BAS)
Fan Coil state and text Tracer SC state and text
1 - Auto 2 - Auto
2 - On 1 - On