Trane Trane Communicating Thermostats (BACnet) Thermostat User Manual


 
BAS-SVP10A-EN 43
Trane Communicating Thermostat Points List
TStat_HeatPump_Trane Template
Cooling Valve Status MV 27
BI 1 Configuration MV 46
BI 2 Configuration MV 47
UI 3 Configuration MV 48
Pipe Number MV 52
AUX Configuration MV 54
Fan Mode Sequence MV 57
Proportional Band MV 65
Floating Motor Timing MV 76
On Off Control CPH MV 77
Table 44. Points Available in the TStat_Fan_Coil_Trane Template (continued)
Tracer SC Point Name
TStat Device Point
Name
Point
Type
Point
Instance
Data
Normaliza-
tion
Table 45. Points Available in the TStat_HeatPump_Trane Template
Tracer SC Point Name
TStat Device Point
Name Point Type
Point
Instance
Data
Normaliza-
tion
Cool Output 1 Status Y1 Cool BI 26
Cool Output 2 Status Y2 Cool BI 27
Diagnostic Present Service Alarm BI 39
Dirty Filter Alarm Filter Alarm BI 38
Discharge Air Temperature Supply Temperature AI 16
Display Temperature Scale Temperature Scale BV 47
Fan Mode BAS Fan Mode MV 15
Fan Output Status G Fan BI 25
Heat Cool Mode Request System Mode HP MV 13 Yes
Heat Output 1 Status W1 Heat BI 28
In Defrost Frost Protection BV 55
Keypad Lockout Keypad Lockout MV 18
Low Temperature Alarm Frost Alarm BI 36
Minimum Heating Cooling Setpoint
Differential
Deadband AV 52
Occupancy Input Local Motion BI 33
Occupancy Request Occupancy Command MV 12 Yes
Occupancy Status Effective Occupancy MV 34 Yes
Occupied Cooling Setpoint Occupied Cool Setpoint AV 43
Occupied Heating Setpoint Occupied Heat Setpoint AV 42
Outdoor Air Temperature Outdoor Temperature AV 9
Reversing Valve Reversing Valve BI 30
Space Temperature Active Room Temperature AV 7
Supply Fan Configuration Command Fan Control BV 62
Supply Fan Failure Fan Lockout Alarm BI 40
Timed Override Duration Setpoint Temporary Occupancy Time MV 61
Unoccupied Cooling Setpoint Unoccupied Cool Setpoint AV 45
Unoccupied Heating Setpoint Unoccupied Heat Setpoint AV 44
PI Heating Demand AV 20
PI Cooling Demand AV 21
Heating Setpoint Limit AV 48
Cooling Setpoint Limit AV 49